28 Technical Bulletin—TC-9102
Table 3: Factory-Set Parameters
Comfort Set Point Heating 20°C +/-3 K Remote Set Point. See Note 2.
-1 K 12-28°C Remote Set Point
Comfort Set Point Cooling 22°C +/-3 K Remote Set Point. See Note 2.
+1 K 12-28°C Remote Set Point
Prop. Band Heating -2 K -1 K when RED jumper OUT. See Note 1.
Integral Time Heating 4 minutes Disabled when BLUE jumper OUT. See Note 1.
Standby Bias Heating -2 K
Night Bias Heating -4 K
Prop. Band Cooling +2 K +1 K when RED jumper OUT. See Note 1.
Integral Time Cooling 4 minutes Disabled when BLUE jumper OUT. See Note 1.
Standby Bias Cooling +2 K
Night Bias Cooling +4 K
Heating Valve Stroke (PAT) 60 seconds +/- 1% Dead Band
Heating Valve Cycle (DAT) 300 seconds 5% minimum On/Off
Heating Stage 1 Load (2St) 50 % 5% differential
Cooling Valve Stroke (PAT) 60 seconds +/- 1% Dead Band
Cooling Valve Cycle (DAT) 300 seconds 5% minimum On/Off
Cooling Stage 1 Load (2St) 50 % 5% differential
Fan On/Off Differential 1 K
Fan always On in Comfort No Yes = Fan On in zero energy band in Comfort.
Min. Fan Output (0-10 VDC) 50 %
Low Limit Set Point 12°C
Low Limit Differential 2 K
Winter Compensation Disabled Requires Outdoor Air Temp via Bus when enabled.
Winter Set Point 10°C
Winter Authority Slope -0.1
Winter Authority Limit -3 K
Summer Compensation Disabled Requires Outdoor Air Temp via Bus when enabled.
Summer Set Point 24°C
Summer Authority Slope 0.2
Summer Authority Limit 5 K
Room Temp Filter Const. 10 seconds
Remote S.P.Filter Const. 60 seconds
Common Set Point 0°C Valid range = -3 to 28. See Note 2.
Unit Mount Sensor No Yes = Hard wired temperature sensor is used and
TM-9180 is connected.
Note 1: Controllers are delivered from the factory with the RED
jumper “IN” and the BLUE jumper “OUT” unless otherwise
specified.
Note 2: When the Remote Set Point is +/-3 K, the Common Set Point
may be set to the desired mean room temperature (e.g. 21°C)
and the Comfort Set Point Heating and Comfort Set Point
Cooling set as biases of -1K and +1K, respectively.
Factory-Set
Parameters