Technical Bulletin—TC-9102 29
The following table lists the parameters which are available for
monitoring by Metasys supervisory systems. For details of configuration
procedures and override possibilities, refer to the technical documentation
of the system which is to be used.
Table 4: Supervisory System Parameters
Parameter Description Units Tag Name Function
Room Temperature °C AI1 Read
Remote Set Point °C or K AI2 Read
Working Set Point Heating °C WSP1 Read
Working Set Point Cooling °C WSP2 Read
Control Output Heating % OCM1 Read
Control Output Cooling % OCM2* Read
Heating/Cooling Mode Cool/Heat L1A* Read
Operating Status Comfort/Standby/Night/Off MODS Read
Alternate Mode Off/On ALT Read
Window Contact Closed/Open WIN Read
Occupancy Sensor Occupied/Unoccupied OCC Read
Low Limit Mode Off/On AFM Read
Winter Set Point Compensation K WAC Read
Summer Set Point Compensation K SAC Read
Requested Operating Mode Comfort/Standby/Night/Off MODC Write
Set Outdoor Temperature °C XAI4 Read/Write
Set Common Set Point °C or K PM6K1 Read/Write
On/Off Fan Control:
Fan Status Off/On DO2 Read
3-Speed Fan Control:
Fan Speed 1 Off/On DO5 Read
Fan Speed 2 Off/On DO6 Read
Fan Speed 3 Off/On DO7 Read
Fan Override Auto/Hold FOV Read
Fan Speed Controller:
Control Output Fan % OCM3 Read
*Note: For 0-10 VDC control signal outputs, OCM1 and OCM2 operate
in parallel and indicate the output level in Heating or Cooling.
Therefore, at the supervisory system, OCM1 should be monitored
as the “Heating/Cooling Control Output” and L1A can be
monitored to indicate whether the controller is in heating or
cooling mode. (Requires Metasys Release 9.0 or later.)