Pressure Actuated “Low Flow”Water Regulating Valve
Introduction
The V46SA is a direct acting, “all range”,
pressure actuated modulating valve, used to
control the waterflow to a condenser by directly
sensing pressure changes in a non-corrosive
refrigerant circuit. The V46SA is specially
designed for use on equipment requiring a low
condenser waterflow such as icemakers, small
heatpumps and watercoolers.
The springhousing and power element are
rolled to the valve body.
Rubber diaphragms seal the water away from
the range spring and bellows part so these are
not submerged in water where they would be
subject to sedimentation and corrosion.
The valve can be ordered style 5 (without
capillary), style 13, style 34 and style 50 (incl.
75 cm capillary).
The capillary part will be delivered separated
from the valve.
V46SA Pressure Actuated "Low Flow"
Water Regulating Valve
Feature and Benefits
! Valve designed for low flow.
Designed to prevent cavitation and water
hammer at low water flow applications.
! “All range” power element and
spring housing.
Reduces stock. Only one valve for all non-
corrosive refrigerants.
! Small dimensions.
Easy to fit in “small dimension” equipment.
! Pressure actuated
Fast response to pressure increase.
! Various pressure connection
styles.
Possibility to meet the legislation in your
country.
! High refrigerant pressure
resistant bellows.
Refrigerant pressure may increase up to
28 bar without bellow damage.
Question and Answer IconNeed help?

Do you have a question about the Johnson Controls V46SA Series and is the answer not in the manual?

Johnson Controls V46SA Series Specifications

General IconGeneral
BrandJohnson Controls
ModelV46SA Series
CategoryControl Unit
LanguageEnglish

Summary

Introduction

Feature and Benefits

Mounting

Adjustment

Valve Capacity

Pressure Connections

Style 13 (excl. valve depressor)

Features 75 cm capillary and 7/16-20 UNF flare nut connection.

Style 45 A (incl. valve depressor mounted into flare)

Includes 75 cm capillary and 7/16-20 UNF flare nut.

Style 34

Comes with 75 cm capillary and 1/4" tube for braze connection.

Style 50 (incl. valve depressor mounted into machined flare)

Supplied with 75 cm capillary, 7/16-20 UNF flare nut, and copper sealring.

Style 5

Features a 7/16-20 UNF connection.

Dimensions

Repair and Replacement

Specifications

Installation

Adjustments

Raise or lower the valve opening point by turning the adjusting screw. Use a pressure gauge for precision.

System check

Run the system through at least one complete operating cycle to verify correct valve operation.

Repair and replacement

Field repair is not possible. Contact nearest supplier for defective units and state type-model number.