April, 2010
24-10239-413 Revision A
S300
Series
S300-DIN-RDR2S
Hardware Installation Manual

Other manuals for Johnson Controls S300 Series

Questions and Answers

  • J
    Jennifer LiAug 14, 2025
    What to do if red light illuminates and access is not granted on Johnson Controls S300 Control Unit?
    • B
      Brittany HarrisAug 14, 2025
      If the red light illuminates or there is no reader light when a card is used and access is denied on your Johnson Controls Control Unit, consider the following: * Ensure the Time zone, Reader, Issue Level, and Facility Code are correct. * Verify the card is in the database. * Confirm the correct card type is being used. * Swipe the card in the correct direction. * Test the reader for functionality. * Replace the card if damaged. * Inspect and repair the cabling. * Replace the PCB if it has failed. * Avoid multiple proximity cards near the reader.
  • B
    Brian QuinnAug 18, 2025
    Why is there card or data loss from database of Johnson Controls S300?
    • D
      Danny MoralesAug 18, 2025
      If you experience card or data loss from the database of your Johnson Controls Control Unit, the following steps may help: * Eliminate any noise on the power line. * Ensure proper grounding of the system. * Replace the CK720 board if it is defective.
  • J
    janice60Aug 21, 2025
    What to do if Johnson Controls S300 system restarts continuously?
    • B
      bennettkimberlyAug 21, 2025
      If your Johnson Controls Control Unit system restarts continuously, it could be due to several reasons: * Ensure the system is properly grounded. * Stabilize the power supply to eliminate severe power variations. * Replace the CK720 board if it is defective.
  • B
    bradshawandrewAug 25, 2025
    Why is the alarm not reporting on Johnson Controls S300 Control Unit?
    • J
      Jessica VargasAug 25, 2025
      If the alarm is not reporting on your Johnson Controls Control Unit, here's what you can check: * Activate the alarm in the appropriate time zone if it is suppressed. * Define the associated input point. * Check and repair any bad wiring or issues with the input device.
  • W
    William TannerAug 27, 2025
    How to fix PIN Code function not operating on Johnson Controls S300 Control Unit?
    • A
      Amber WeissAug 28, 2025
      If the PIN Code function is not operating on your Johnson Controls Control Unit, consider the following: * Program the PIN as part of the access condition. * Inspect and fix the wiring from the keypad to PCBA if there's a broken or incorrect wire. * Replace the keypad if it is defective.
  • R
    ronniesmithAug 31, 2025
    What to do if the reader is down on Johnson Controls Control Unit?
    • L
      lowerytracyAug 31, 2025
      If the reader is down on your Johnson Controls Control Unit, you should: * Correct the wiring from the reader to RDR2 or RDR2S. * Assign the reader. * Replace the defective RDR2 or RDR2S.
  • R
    rkellySep 3, 2025
    Why door will not go into “Override Mode” on Johnson Controls S300 Control Unit?
    • J
      Jeanne BradleySep 4, 2025
      If the door of your Johnson Controls Control Unit won't go into 'Override Mode' but still grants access with a card, it may be because: * The Override time zone is incorrectly programmed or not programmed at all, so check and program it correctly. * The Override option is not set, so ensure you set the Override option.
  • A
    Antonio CampbellSep 6, 2025
    Why red or green lamp does not illuminate on Johnson Controls S300 Control Unit?
    • C
      Connie CowanSep 6, 2025
      If the Red or Green lamp does not illuminate on your Johnson Controls Control Unit, but access is still either denied or granted when a card is used, it could be due to: * An open wire at the lamp connection, so check and repair the wire. * A burned-out lamp bulb, so replace the bulb. * A defective Reader Add-on board, so replace the board.
  • M
    Mr. William MerrittSep 10, 2025
    How to fix holiday time zones not followed on Johnson Controls Control Unit?
    • W
      watsonlindseySep 10, 2025
      If Holiday time zones are not being followed on your Johnson Controls Control Unit, it is likely due to improperly programmed Holiday time zones or Holiday dates. Correctly program the Holiday time zones or dates to resolve this issue.

Summary

HARDWARE INSTALLATION

INSTALLATION

Covers procedures for setting up the RDR2S module.

DC Power Source

Details the DC power requirements and wiring for the RDR2S.

Chassis Grounding

Explains how to properly ground the RDR2S module.

Reader 1 Signal Descriptions

Detailed pinout and function for Reader 1.

Reader 2 Signal Descriptions

Detailed pinout and function for Reader 2.

Cable Requirements

Specifications for cable types and maximum segment lengths.

Power Supply

Wiring instructions for connecting power supplies, including daisy-chaining.

Power Requirements

General power specifications for the RDR2S module.

Tamper Switch Wiring

How to connect and program the tamper switch.

Sample Application Diagrams

Illustrative diagrams for common RDR2S applications.

Ground and Grounding Cable Shields

Guidelines for grounding the RDR2S unit and its cables.

Grounding Cable Shields

Guidelines for grounding cable shields for EMC and reliability.

SETUP AND ADJUSTMENTS

Configuration Jumpers

Guide to setting configuration jumpers for various functions.

RS485 Connection

Information and settings for RS485 network communication.

Setting the End-of-Line Switch (SW1)

Instructions for setting the RS485 termination switch.

Address Switches (SW3)

Introduction to the address switch for module identification.

Terminal Addressing

Details on setting terminal addresses for different controllers.

MAINTENANCE

Routine Maintenance

Regular maintenance tasks for the RDR2S module.

Testing Procedure

Steps to verify proper RDR2S operation using LEDs and card tests.

Real Time Clock Battery (Lithium Battery) Replacement

Procedure for replacing the RTC battery.

TROUBLESHOOTING

Table of common issues and their possible causes for the access control system.

Johnson Controls S300 Series Specifications

General IconGeneral
SeriesS300 Series
ManufacturerJohnson Controls
CategoryControl Unit
Enclosure RatingIP20
Communication ProtocolBACnet MS/TP
MountingDIN rail