66 VAV Controller—Variable Air Volume Controller
Table 26: Dual Duct Hardware Point Assignments and Options
Point Type Point
Name
HVAC PRO for Windows Configuration
Assignments and Defaults
HVAC PRO for Windows
Configuration Options
Analog Inputs
AI 1 Zone Temperature None
AI 2 Unused Rename
Cooling Setpoint
Warmer/Cooler Adjust
AI 3 Unused Rename
Heating Setpoint
AI 4 Cold Deck Delta P None
Supply Delta P None
AI 5 Hot Deck Delta P None
Unused Rename
AI 6 Discharge Air Temp None
Exhaust Delta P None
Unused Rename
Binary Inputs
BI 1 Unused Rename
Occupied
BI 2 Unused Rename
Standby
BI 3 Unused Rename
Shutdown Box Open
BI 4 Unused Rename
Shutdown Box Closed
Momentary BI
BI 5 Unused Rename
Temp Occupancy
Boost
Binary Outputs
BO 1 Damper Open None
Cold Deck Open None
BO 2 Damper Close None
Cold Deck Close None
BO 3 Heating/Cooling Changeover None
Hot Deck Open None
BO 4 Unused Rename
Hot Deck Close None
BO 5 Unused Rename
Exhaust Open None
BO 6 Unused Rename
Exhaust Close None
BO 7 Unused Rename
Basebd Heat None
Basebd Open None
Lights On None
BO 8 Unused Rename
Basebd Close None
Lights Off None