T9800 series BACnet MS/TP Networked Thermostat Controller Technical Bulletin
Rev 1.4
10 | P a g e
BO object to control the valve.
FRST-PRT
Frost protection, enable or disable the frost protection function.
TIO2-ESP
When app support the TIO2-ESP, if the TIO2-ESP control by manual, user can enable or disable
TIO2-ESP output by this point.
FH-FAN
When app support floor heating, this point can disable or enable the fan speed function when only
floor heating work.
MUTE
User can control the buzzer for keys by this point to mute or not.
ECM-PLY
When app support ECM function, this point can enable or disable the related relay output for ecm
function.
ZN-T
The current temperature.
ZNT-SP
The current set point.
OFFSET
This point can correct the current temperature.
ZN-H
The current humidity.
UNOCC-CLG-SP
Working in un-occupancy, the device cooling mode set-point.
UNOCC-HTG-SP
Working in un-occupancy , the device heating mode set-point.
FP-SP
Frost set point, when the frost protection enable this point define condition to start the frost
protection.
STG-DFFR
Stage difference, when app support the FCU heating and floor heating work together. Setting this
point to start FCU heating function when floor heating can’t meet objective.
SMPL-TM
Sample time, when app support modulation control, this point define the control period.
PB
Proportion band.
KI
Integral parameter.
HTRSS
This point define the dead band for ON/OFF control.
DMP-OPEN-TIME
Damper open time, when app is the AHU, user can set this point for different damper requirement.
BL-TIMER
Black lighter time.