TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
8. Set the time to the time at which the event should
occur and press the Save icon.
9. Press Save to save the event and press the return
icon to return to the main scheduler screen.
10. Press to save and to return to the
previous screen.
Overriding the Occupancy Mode
The TEC supports a manual override of all other
schedule sources (for example, Schedule, Occupancy
BI, and temporary occupancy). To set the override:
1. Press the Menu icon.
2. Press Schedule
3. Press Schedule Options.
4. Press Manual Occupancy Mode and select
Occupied, Unoccupied, or No Override.
5. Press to save and to return to the
previous screen.
This option is also exposed to the BAS through the
point OCCOVRD-MODE.
Enabling Optimal Start
The TEC supports an advanced optimal start algorithm.
The algorithm works in conjunction with a local
schedule to pre-heat or pre-cool the zone before
scheduled occupancy periods begin, in order to bring
the zone to the desired occupied setpoint when the
scheduled occupancy period begins. Occupant comfort
is ensured while automatically minimizing energy
usage. This algorithm creates a model of the zone
being controlled and automatically determines when to
start the equipment before the scheduled transition to
Occupied. The start time automatically adjusts daily in
order to minimize the time between reaching setpoint
and entering Occupied state. To enable this feature:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Optimal Start Enable and select Yes.
5. Press to save and to return to the
previous screen.