FlexSys Thermostat Zone Controller / LCD Touch Screen
TEC - 3620
Model:
©2016 Johnson Controls | The performance specications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specications, consult the local
Johnson Controls ofce. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
© 2016 AirFixture, LLC
1
Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with
Dehumidification Capability Installation Instructions
QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series On/Off or Floating Fan Coil and
Zoning Thermostat Controllers are stand-alone and
field-selectable BACnet® Master-Slave/Token-Passing
(MS/TP) or N2 networked devices provide control of:
local hydronic reheat valves
pressure-dependent variable air volume (VAV)
equipment with or without local reheat
two- or four-pipe fan coils
cabinet unit heaters
other zoning equipment using an on/off or floating
control input
The networked models feature a field-selectable
Building Automation System (BAS) BACnet MS/TP or
N2 communication capability that enables remote
monitoring and programming for efficient space
temperature control. All models include a USB port
configuration that reduces installation time by allowing
simple backup and restore features from a USB drive,
which enables rapid cloning of configuration between
like units.
Some models have occupancy sensing capability built
into the device. These thermostat controllers maximize
up to 30% energy savings in high-energy usage
commercial buildings, such as schools and hotels,
during occupied times by using additional standby
setpoints.
All models feature an intuitive UI with backlit display
that makes setup and operation quick and easy.
Multiple fan configurations are supported for fan coil
equipment types:
single-speed
multi-speed (two or three discrete speeds)
variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan
coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the
thermostat controller monitors space humidity and
activates dehumidification control as necessary. Heat
and/or reheat is used as required to maintain the space
temperature. For optimal dehumidification
performance, use a fan coil unit that has a multi-speed
or variable-speed fan (VSF).
IMPORTANT: The TEC3000 Series Thermostat
Controller is intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the
thermostat controller.
IMPORTANT : Le TEC3000 Series Thermostat
Controller est destiné à transmettre des données
entrantes à un équipement dans des conditions
normales de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du thermostat controller
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du thermostat
controller.
TEC3310-00-000, TEC3311-00-000, TEC3312-00-000, TEC3313-00-000,
TEC3610-00-000, TEC3611-00-000, TEC3612-00-000, TEC3613-00-000

Questions and Answers

  • M
    Michael BradleyAug 14, 2025
    What to do if my Johnson Controls TEC-3620 Controller shows 'Dirty Filter'?
    • M
      Melissa CookeAug 14, 2025
      If your Johnson Controls Controller displays a 'Dirty Filter' message, it means the equipment connected to the BI configured for a Dirty Filter alarm is triggering the alarm. Replace the filter in the equipment according to the manufacturer's instructions.
  • T
    Teresa AllenAug 17, 2025
    What does 'Service' mean on my Johnson Controls TEC-3620 Controller?
    • G
      glennmaryAug 18, 2025
      If your Johnson Controls Controller displays 'Service', it indicates that equipment connected to the BI configured for a Service alarm is triggering the alarm. Service the equipment per the manufacturer's recommendation.
  • A
    allison30Aug 21, 2025
    What to do if Johnson Controls TEC-3620 Controller displays 'Open Window'?
    • I
      Ian BoydAug 21, 2025
      If your Johnson Controls Controller displays 'Open Window', it means the switch connected to the BI configured for Open Window is sensing that the window is opened, and control has shut down. First, close the window to resume control. Next, check sensor functionality with an ohmmeter and verify the wiring to the TEC.
  • M
    Matthew MillerAug 25, 2025
    How to fix 'Fan Lock' on Johnson Controls Controller?
    • M
      michael24Aug 25, 2025
      If your Johnson Controls Controller displays 'Fan Lock', it means that the switch connected to the BI configured for Fan Lock did not sense airflow within 10 seconds of starting the fan, and control has been shut down. First, inspect the equipment to ensure the fan functions. Next, check sensor functionality with an ohmmeter and verify wiring to the TEC. Then, reset the fault by entering the menu, selecting Fault Status, and selecting the Fan Lock.
  • S
    Samantha SweeneyAug 27, 2025
    Why does my Johnson Controls TEC-3620 show 'Remote Zone Temp Fail'?
    • A
      ashleyraymondAug 27, 2025
      The 'Remote Zone Temp Fail' message on your Johnson Controls Controller indicates that the External Zone Temperature sensor has been disconnected or has failed. Check the wiring of the sensor. If intentionally disconnected, reset sensors through the menu.
  • B
    Brenda FrazierAug 30, 2025
    What does 'Supply Temp Fail' mean on my Johnson Controls TEC-3620?
    • T
      Timothy TaylorAug 30, 2025
      The 'Supply Temp Fail' message on your Johnson Controls Controller indicates that the External Supply Temperature sensor has been disconnected or has failed. Check the wiring of the sensor. If intentionally disconnected, reset sensors through the menu.
  • E
    Erik MorenoSep 3, 2025
    What to do if Johnson Controls TEC-3620 Controller displays 'Changeover Fail'?
    • S
      sarah82Sep 3, 2025
      The 'Changeover Fail' message on your Johnson Controls Controller means that the Supply Temperature Sensor is not installed, has failed, or has been disconnected and the TEC can no longer detect changeover mode to cool or heat. Follow the same steps as the Supply Temp Fail alarm: check the wiring of the sensor and, if intentionally disconnected, reset sensors through the menu.
  • M
    Michael HumphreySep 7, 2025
    What to do if my Johnson Controls Controller says 'Dehum Unavailable'?
    • K
      kleindeanSep 7, 2025
      If your Johnson Controls Controller displays 'Dehum Unavailable', it means dehumidification is unavailable because the zone humidity sensor has failed. Replace the thermostat controller.
  • T
    toddjohnSep 9, 2025
    What does 'Humidity Unreliable' mean on my Johnson Controls TEC-3620?
    • S
      Sarah ButlerSep 10, 2025
      If your Johnson Controls Controller displays 'Humidity Unreliable', it means the zone humidity reading was reliable and has now failed. If the source of zone humidity was a BAS, check the BAS to ensure that it is still online and providing the TEC with the humidity reading. If removal of the BAS mapping was intentional, reset sensors through the menu.

Summary

Installation Guide

North American Emissions Compliance

Regulatory compliance for FCC and Canadian digital device standards.

Mounting and Location Considerations

Guidelines for optimal thermostat controller placement and mounting.

Thermostat Controller Installation Steps

Step-by-step instructions for physically mounting the thermostat controller.

Thermostat Controller Wiring Guide

Comprehensive instructions for connecting the thermostat controller's wires.

Configuration and Setup

Touchscreen Interface and Home Screen Customization

Overview of the screen, icons, and personalizing the home screen display.

USB Configuration and Firmware Management

Procedures for loading firmware, and backing up/restoring settings via USB.

Network and Communication Setup

Configuration of network settings, including BACnet and N2 communication modes.

HVAC System Type and Control Configuration

Setting unit type, fan configurations, control modes, and sensor inputs.

Occupancy, Scheduling, and Advanced Control Setup

Managing occupancy sources, schedules, overrides, optimal start, and sensors.

Auxiliary Outputs and Commissioning Mode

Configuring auxiliary outputs and entering commissioning mode for testing.

Troubleshooting

Fault List and Probable Causes

Lists common faults, their likely causes, and recommended solutions.

Symptom-Based Troubleshooting Guide

Addresses common operational symptoms and provides corresponding solutions.

Technical Specifications

Power, Network, and Sensor Specifications

Details on power requirements, network guidelines, and temperature sensor types.

Environmental, Compliance, and Shipping Data

Ambient conditions, regulatory compliance, and shipping weight information.

Johnson Controls TEC-3620 Specifications

General IconGeneral
ModelTEC-3620
Input Voltage24 VAC
DisplayLCD
Communication ProtocolBACnet MS/TP
Controller TypeProgrammable
Housing MaterialPlastic
TypeController
Humidity Range5 to 95% RH, non-condensing
Output TypeAnalog and Digital
Temperature Range32°F to 122°F (0°C to 50°C)