FlexSys Thermostat Zone Controller / LCD Touch Screen
TEC - 3620
Model:
©2016 Johnson Controls | The performance specications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specications, consult the local
Johnson Controls ofce. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
© 2016 AirFixture, LLC
37
Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
37
Technical Specifications
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with
Dehumidification Capability
Power Requirements 19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
Relay Contact
Rating
On/Off or
Floating Control
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Fan Relay Output Rating 19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Auxiliary Output Rating/Triac
Output
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush
Binary Inputs Dry contact across terminal COM to terminals BI1, BI2, or COS
Analog Inputs Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
terminal COM to terminals R SEN or COS
Temperature Sensor Type Local 1k ohm platinum sensor
Wire Size 18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
MS/TP Network Guidelines Up to 100 devices maximum per Network Automation Engine (NAE);
4,000 ft (1,219 m) maximum cable length
Temperature
Range
Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Minimum Deadband 2F°/1C° between heating and cooling
Occupancy Sensor Motion
Detection (Occupancy Sensing
Models)
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
Ambient
Conditions
Operating 32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
Compliance BACnet
International
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific
Controller (B-ASC)
United States UL Listed, File E27734, CCN XAPX, Under UL60730
FCC Compliant to CFR 47, Part 15, Subpart B, Class B
Canada UL Listed, File E27734, CCN XAPX7, Under E60730
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance
with the essential requirements and other relevant provisions of the EMC Directive
and the RoHS Directive.
Australia and
New Zealand
RCM Mark, Australia/NZ Emissions Compliant
Shipping
Weight
Models without
Occupancy
Sensor
0.75 lb (0.34 kg)
Models with
Occupancy
Sensor
0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.