TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
38
Equipment Setup
(Cont)
Supply Temp Sensor* Nickel Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
* Supply temp type = analog sensor
Supply Temp Offset* 0°F -5 to 5°F (-3 to 3°C)
* Supply temp type = analog sensor
Trend EFF-ZNT
-50 to 250°F (-45.56 to 121.11°C)
EFF-SETPOINT
45 to 100°F (7.22 to 37.78°C)
EFF-ZNH
0 to 100%RH
B1 Status
On or Off
B2 Status
On or Off
EFF-OAT
-50 to 250°F (-45.56 to 121.11°C)
EFF-SAT
-50 to 250°F (-45.56 to 121.11°C)
FANSPD-S
On or Off
HTG-O
0 to 100%
CLG-O
0 to 100%
System Status Occupancy Source Local Schedule Occupancy BI
Temp Occ BI
Temp Occ
Occ Override
Local Schedule
BAS Schedule
Occupancy Sensor
Unit Status Cooling System Fault
Airflow Fault
Open Window
Control Off
Unreliable Temperature
Dehumidification
Idle
Cooling
Heating
Cooling Unavailable
Heating Unavailable
Cooling Unavailable due to Changeover
Cooling Unavailable due to OA Temp
Cooling Unavailable due to Control Mode
Heating Unavailable due to Changeover
Heating Unavailable due to OA Temp
Heating Unavailable due to Control Mode
Supply Air Temperature 75°F -50 to 250°F (-45 to 121°C)
Table 10: Menus and Submenus (Part 6 of 8)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values