EasyManua.ls Logo

Johnson Controls TEC3310 - User Manual

Johnson Controls TEC3310
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TEC3000 Series On/Off or Floating Fan Coil and Individual Zone
Thermostat Controllers with Dehumidification Capability
Installation Instructions
1
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers are stand-alone and
field-selectable BACnet® MS/TP or N2 networked devices that provide control of the following:
local hydronic reheat valves
pressure-dependent variable air volume (VAV) equipment with or without local reheat
two- or four-pipe fan coils
cabinet unit heaters
other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring and programming for efficient space temperature control.
All models include a USB port configuration that reduces installation time by allowing simple backup and restore
features from a USB drive, which enables rapid cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick
and easy. Multiple fan configurations are supported for fan coil equipment types:
single-speed
multi-speed (two or three discrete speeds)
variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or
without reheat. When no heating is required, the thermostat controller monitors space humidity and activates
dehumidification control as necessary. Heat and/or reheat is used as required to maintain the space temperature.
For optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
TEC3000 Series On/Off or Floating Fan Coil and Individual
Zone Thermostat Controllers with Dehumidification
Capability
Installation Instructions
TEC3310-xx-xxx, TEC3311-xx-xxx, TEC3312-xx-xxx, TEC3313-xx-xxx,TEC3610-xx-xxx, TEC3611-xx-xxx, TEC3612-xx-xxx, TEC3613-xx-xxx
Part No. 24-10787-6, Rev.
F
Issued July 2018
(barcode for factory use only)
24-10787-6, Rev. F
*24107876F*

Questions and Answers

  • B
    Betty GordonSep 2, 2025
    What does 'USB Malfunction' mean on my Johnson Controls TEC3310?
    • K
      Karen JohnsonSep 2, 2025
      If your Johnson Controls Controller displays 'USB Malfunction', it means a USB drive has malfunctioned and drawn too much current. First, try inserting the USB drive again. If that doesn't work, try a different USB drive. If the problem persists, you might need to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • D
    danny16Sep 14, 2025
    What does 'Zone Temp Unreliable' mean on my Johnson Controls Controller?
    • R
      Rachel YoungSep 14, 2025
      If your Johnson Controls Controller displays 'Zone Temp Unreliable', it means all sources of zone temperature, including the onboard sensor, are unreliable. You will need to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • B
    Bethany HutchinsonAug 31, 2025
    Why does my Johnson Controls TEC3310 Controller show 'Fan Lock'?
    • E
      estesjeromeAug 31, 2025
      If your Johnson Controls Controller displays 'Fan Lock' and control has shut down, it means the switch connected to the BI configured for Fan Lock didn't sense airflow within 10 seconds of starting the fan. Here's how to address it: First, inspect the equipment to ensure the fan functions. Next, check the sensor functionality with an ohmmeter and verify the wiring to the TEC. Then, reset the fault by going to the menu, selecting Fault Status, and choosing Fan Lock. If the problem persists, you may need to order replacement units and return the affected devices to Johnson Controls under the RMA program.
  • P
    Peter SimmonsSep 16, 2025
    Why can't my Johnson Controls TEC3310 access a USB drive?
    • T
      Todd MorrisonSep 16, 2025
      If the Johnson Controls Controller is unable to access a USB drive, the drive might be formatted as NTFS or another unsupported format. The TEC supports FAT and FAT32 formats only. Reformat the USB drive, or try a different USB drive with a supported format. Alternatively, the USB drive may be defective, so try a different one.
  • R
    Richard TaylorSep 15, 2025
    Why does my Johnson Controls TEC3310 show an error when restoring settings from a backup?
    • M
      Mrs. Stephanie NewmanSep 15, 2025
      If the controller provides an error when trying to restore settings from a backup on your Johnson Controls Controller, the USB drive may be defective, the restore file may be corrupt, or the restore file may be from an incompatible model TEC. Try a different USB drive, try restoring a different backup file, and ensure that the backup file being restored was from the same model TEC.
  • E
    emilyjohnsonSep 23, 2025
    Why is the temperature displayed lower than actual on my Johnson Controls TEC3310 Controller?
    • P
      Paul RussellSep 23, 2025
      If the temperature displayed on your Johnson Controls Controller is lower than the actual room temperature, cold air drafts may be entering the back of the TEC, or air may be forced through the TEC from a nearby vent. To fix this, seal any holes behind the TEC to reduce drafts, or move the location of the TEC or change the venting to prevent air from being forced through the TEC.
  • S
    Sheila WilliamsAug 27, 2025
    How to resolve a 'Board Mismatch' error on my Johnson Controls TEC3310 Controller?
    • A
      Ashley WolfAug 28, 2025
      If your Johnson Controls Controller displays 'Board Mismatch', it means the baseboard and CPU board are not correctly paired. The TEC will show an error message with the model numbers of both boards. To fix this, match the baseboard to its corresponding CPU board.
  • J
    Joshua AustinAug 27, 2025
    What does 'Changeover Fail' mean on my Johnson Controls Controller and how to fix it?
    • E
      Eric KempAug 27, 2025
      If your Johnson Controls Controller displays 'Changeover Fail', it indicates that the Supply Temperature Sensor is either not installed, has failed, or has been disconnected. As a result, the TEC can't detect the changeover mode for cooling or heating. You can follow the same troubleshooting steps as for a 'Supply Temp Fail' alarm.
  • R
    Ronald EdwardsAug 26, 2025
    Why is the TEC3000 zone temperature not changing fast enough on my Johnson Controls TEC3310?
    • J
      Jacob PetersAug 26, 2025
      If the TEC3000 zone temperature on your Johnson Controls Controller isn't changing fast enough compared to a calibrated sensor, it might be because the TEC3000 is set up for larger spaces by default when a proportional device is active. To resolve this, go to Control Setup > Tuning > Equipment Size and select 'Oversized'.
  • M
    Michelle Snow MDAug 25, 2025
    How to troubleshoot a 'Supply Temp Fail' error on a Johnson Controls Controller?
    • P
      Paul WilliamsonAug 26, 2025
      If your Johnson Controls Controller displays 'Supply Temp Fail', the external supply temperature sensor is either disconnected or has failed. You can try these steps: First, check the sensor wiring. If intentionally disconnected, reset the sensors by going to the menu, then Control Setup, and selecting Inputs. If the problem continues, order replacement units and return the affected devices to Johnson Controls under the RMA program.

Summary

Installation Instructions

Applications

Details the standalone and networked applications for TEC3000 series controllers.

Installation Steps

Covers parts, location, and the physical process of installing the thermostat.

Wiring Diagrams and Connections

Setup and Adjustments

USB Port Operations

Instructions for firmware updates and configuration backup/restore using USB.

Fan Configuration

Details on setting fan types, speeds, and modes for fan coil units.

Dehumidification Control Configuration

Configuration details for enabling and adjusting dehumidification on fan coil units.

PID;PRAC+ Automatic Control Tuning

How to reset and manage the controller's PID tuning for optimal performance.

Occupancy Configuration

Methods for setting occupancy schedules and sources for the thermostat.

Commissioning Mode

How to test equipment wiring and functionality during installation.

Troubleshooting and Specifications

Fault List

Lists common faults, probable causes, and solutions for the TEC3000 controller.

Troubleshooting Details

Provides detailed explanations for symptoms and their resolutions.

Johnson Controls TEC3310 Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3310
CategoryController
LanguageEnglish

Related product manuals