6021974-UIM-A-1120
36 Johnson Controls Ducted Systems
Lit, then flashes during the boot-up sequence of the RRS
Economizer Controller
Not lit when there are no Alarms active
Double-flash/pause continuously when Alarms are active
• SA BUS (green)
Will not be lit
Menu Structure
The top level menus are:
STATUS
ALARMS
SUMMARY ECONOMIZER, POWER EXHAUST,
COMPRESSOR
COMMISSION
CONTROLLER SETTINGS
UPDATE
DETAILS
SELF TEST
VIEW RESULTS
NOTE: Your menu parameters will be different depending on
your configuration. Refer to the RRS Economizer
Control Quick Start Guide P/N 5292230-USG available
from your equipment dealer or distributor.
RRS Economizer Controller Parameter Menu Functions
There are several "conditional" parameters within the menu.
Parameters for temperature, humidity and CO
2
inputs are only
shown in the menu once sensor presence has been detected.
Parameters associated with a function are only shown in the
menu when that function is enabled.
Smart Equipment™ Economizer Sequences
Units with the Smart Equipment™ Control will have a factory
option or field kit with Johnson Controls Economizer.
Several functions can drive the economizer, including: minimum
position, free cooling, economizer loading, and minimum
outdoor air supply.
Economizer Minimum Position
The economizer minimum position is set during occupied mode
when outside air is not suitable for free cooling. The position of
the damper is set proportionally between the "Economizer
Minimum Position and the Economizer Minimum Position Low
Speed Fan" set points, in relationship to the VFD output
percentage. On a constant volume single speed supply fan
system both set-points should be set to the same value.
Free Cooling
Four types of free cooling options are available: dry bulb
changeover, single enthalpy, dual enthalpy changeover, and
Auto.
Dry Bulb Changeover
For dry bulb economizer operation, the outside air is suitable for
free cooling if the outside air temperature is 1°F below the
Economizer OAT Enable Setpoint and 1°F below the Return Air
Temperature.
Free cooling is no longer available if the outside air temperature
rises above either the Economizer OAT Enable setpoint or the
return air temperature.
Single Enthalpy Changeover
For single enthalpy economizer operation, the outside air is
suitable for free cooling if the outside air enthalpy is at least 1
BTU/lb below the Economizer Outside Air Enthalpy Setpoint
and the outside air temperature is no greater than the RAT plus
9°F.
If the outside air temperature rises above the RAT plus 10°F,
free cooling is no longer available. The outside air temperature
must drop to no greater than RAT plus 9°F to enter free cooling
again.
Free cooling is no longer available if the outside air enthalpy
rises above the Economizer Outside Air Enthalpy Setpoint.
Dual Enthalpy Changeover
For dual enthalpy economizer operation, the outside air
enthalpy must be lower than the return air enthalpy by 1 btu/lb
AND the outside air temperature is no greater than the RAT
plus 9°F.
Auto
The control determines the type of free cooling changeover
based on which sensors are present and reliable. Conditions
include:
Return and outside air dry bulb = dry bulb changeover
Return and outside air dry bulb and outside air humidity =
single enthalpy
Return and outside air dry bulb and return and outside air
humidity = dual enthalpy
If either the return or outside air dry bulb sensors are
unreliable, free cooling is not available
Free Cooling Operation
When the control determines that the outside air is suitable, the
first stage of cooling will always be free cooling.
Thermostat
In free cooling, with a thermostat input to Y1, the dampers
modulate to control the supply air temperature to the
Economizer Setpoint +/- 1°F (default 55°F).
If the thermostat provides an input to Y2 and the parameter
Compressors Off in Free Cooling is turned OFF a compressor
output energizes. The economizer dampers continue to

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZE Series and is the answer not in the manual?

Johnson Controls ZE Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZE Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals