15
F 602 CB 139677_R04 April 2017
Wall Shield
• Must be 1” off
the wall and 1”
off the floor.
• With single wall
pipe, the shield
must be 49”.
• With the double
wall pipe, the
shield must be
37” high.
• Both shields
MUST extend
and join in the
corner.
Combustible wall
The wall shield
must extend a
minimum of 7”
(178mm) past
the front corner
of the stove.
The wall shield must
extend a minimum of 7”
(178mm) past the front
corner of the stove.
Corner installation with wall shield
Fig. 18
Parallel installation in a corner with
wall shield
Fig. 17
The wall shield must extend a mini-
mum of 7” (178mm) past the ash lip
of the stove
Wall Shield
• Must be 1” off the
wall and 1” off the
floor.
• With single wall
pipe, the shield
must be 49” high
measured off the
floor.
• With double wall
pipe, the shield
must be 37” high
measured off the
floor.
• Both shields MUST
extend and join in
the corner.
Combustible wall
The wall
shield must
extend a
minimum of
4” (102 mm)
past the side
of the stove
Fig. 20
Controls
Air Valve:
Left = Closed / Right = Open
Door Latch
Fig. 19
Fireplace Mantel and Trim Clearance