EasyManua.ls Logo

Jøtul F 602 ECO - Chimney and flue pipe; Assembling the flue pipe

Jøtul F 602 ECO
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
ENGLISH
Fig. 11 Mounting of external air supply connection
1
2
1. Place the external air supply connection on the outside of
the external air supply adaptor.This works the same way
for both wall and oor outlet.
2. Tighten with screwdriver.
4.4 Location of approval label
Fig. 12 Approval label
A
1. The approval label (A) is located on the bottom of the
stove.
4.5 Chimney and ue pipe
• The replace must only be connected to a chimney and
ue pipe approved for solid fuel replaces with ue gas
temperatures as speci ed in «2.0 Technical Data».
• For ue pipe dimension see “2.0 Technical Data”. NB:
The chimney’s diameter must be at least just as big as the
ue pipe.
Connection to the chimney must be carried out in
accordance with the chimney supplier’s installation
instructions.
Before a hole is made in the chimney, the product should
be test-mounted in order to correctly mark the position of
the replace and the hole in the chimney. See g. 1 for
minimum dimensions.
• Use a ue pipe bend with a sweep hatch to allow sweeping.
Please note that it is extremely important for connections
to have a degree of exibility. This is to prevent any
movement in the installation leading to the formation of
cracks.
For recommended chimney draught, see «2.0 Technical
Data».
NB! The minimum recommended chimney length is 3.5 m
from the ue pipe insert. If the draught is too strong, a ue
pipe damper can be installed and used to reduce the draugh
If a ue damper is tted it shall be of a type, which does not
block the ue totally. The damper shall be easy to operate and
incorporate an aperture within the blade, which in a continuous
area occupies at least 20 cm2 or 3 % of the cross-sectional
area of the blade if this is greater.
The position of the damper shall be recognizable from the
setting of the device.
If a draught regulator is tted the minimum cross sectional
area requirement shall not be applicable but the device shall
be easily accessible for cleaning.
Assembly of ue pipe
The product is assembled for a top outlet as standard.
Fig. 13 Assembling the ue pipe
1
2
1. Pull o the protective paper from the supplied gasket
and attach it to the outside of the ue pipe
2. Insert the ue pipe into the smoke outlet.
Flue pipe is installed in the same way for top and rear outlet.

Related product manuals