Parameter settings
Parameter settings
Code Description Range Standard Comments
01 Set temperature 15–40 °C 28°C Adjustable
02 Defrosting cycle 30–90 min 40 min Depending on model
03 Defrosting – start temperature -30–0 °C -7 °C Depending on model
04 Defrosting – stop temperature 2–30 °C 13°C Depending on model
05 Defrosting time 1–12 min 8 min Depending on model
06 Linking 1–2 1 = off Option
07 Memory function 0–1 1 = auto Option
08
Circulation pump – operating
setting
0–1 0 = on Option
09 Temperature sensitivity 1–5 2 Adjustable
10
Max. difference between
incoming/outgoing water
temperature.
2–20 °C 13°C Adjustable
11 Pool temperature -9–90 °C Actual
12 Outgoing water temperature -9–90 °C Actual
13 Circuit temperature -9–90 °C Actual
15 Outdoor temperature -9–90 °C Actual
START UP
Start up
Check the unit and then start the pump. Check that all the connections for electricity and water have been
made properly.
Check that water does not leak from any of the connections.
Start the unit and re-check that there is no leakage and that water circulates through the system
Check after a period of operation that the air coming out of the pool heat pump is colder than the
outside air.
Set the required temperature on the control panel and allow the unit to run.
The pool heat pump is shut off when the water temperature reaches the required temperature.
When the temperature drops one degree below the set temperature the unit starts automatically.
Moving
In order to move the unit on a flat surface, press down the handle with both hands so that the unit's feet
lift from the ground. The pool heat pump can now be pushed or pulled into the correct position.