EasyManua.ls Logo

Jung KNX - Help in Case of Trouble; Manual Control Not Possible; Output Control Not Possible; None of the Outputs Operational

Jung KNX
13 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
KNX Room actuator 230 V
Ref.-no.: RA 23024 REGHE
12
8 Help in case of trouble
Manual control with keypad not possible
Manual operation not parameterized.
Parameterize manual operation.
Manual operation disabled via the bus.
Enable the manual control mode.
No mains voltage.
Switch on the mains voltage.
Check the fuses.
Output control not possible
Output disabled.
Cancel the state of disabling.
None of the outputs operational
All outputs are disabled.
Cancel the state of disabling.
Permanent manual control mode active.
Deactivate the permanent manual control mode (switch this mode off).
Application software stopped, programming LED flashes.
Make a reset: Disconnect the device from the bus,
reconnect after ca. 5 s.
Operation via the bus impossible
No bus voltage.
Switch on the bus voltage; have the installation
checked by a qualified electrician.
Application software stopped, programming LED flashes.
Make a reset: Disconnect the device from
the bus, reconnect after ca. 5 s..
9 Accessories
Protective cap Ref.-no.: 2050 K
Isolating relay AP Ref.-no.: TR-S
Isolating relay UP Ref.-no.: TR-S REG
Isolating relay UP Ref.-no.: TR-S UP
Thermal valve drive 230 V Ref.-no.: TVA 110 WW

Related product manuals