EasyManua.ls Logo

Kanmor 360e - Adjust Menu

Default Icon
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2003 D 360e - 06/03 16 of 20
Adjust Menu (1 of 2)
Section
Installer
Advanced
Range
Actual
Setting
DescriptionDisplay
B2
The desired room air temperature during an
occupied (Day) period.
(OUTDR DSGN OFF)
35 to 100°F
(2 to 38°C)
The desired room air temperature during an
unoccupied (Night) period.
(OUTDR DSGN OFF)
35 to 100°F
(2 to 38°C)
B2
Mixing setpoint temperature.
(OUTDR DSGN = OFF)
60 to 200°F
(16 to 93°C)
B2
The design outdoor air temperature used in the
heat loss calculation for the heating system. For
setpoint operation, set the OUTDR DSGN to OFF
-60 to 32°, OFF
(-51 to 0°C, OFF)
B2
The design indoor air temperature used in the
heat loss calculation for the heating system.
(OUTDR DSGN OFF)
35 to 100°F
(2 to 38°C)
B3
The design supply water temperature used in
the heat loss calculation for the heating system.
(OUTDR DSGN OFF)
70 to 220°F
(21 to 104°C)
B3
The maximum supply water temperature for the
mixing system
(OUTDR DSGN OFF)
80 to 210°F
(27 to 99°C)
B3
The minimum supply temperature for the
mixing system.
(OUTDR DSGN OFF)
OFF, 35 to 150°F
(OFF, 2 to 65°C)
B3
The minimum temperature allowed for the boiler
target temperature.
(Boiler sensor is present)
OFF, 80 to 180°F
(OFF, 27 to 82°C)
C1
The type of terminal units that are being used
in the heating system.
(OUTDR DSGN OFF)
1 (High Ma
ss
Radiant
2 (Low Mass Radiant
3 (Fancoil)
4 (Fin-tube Convector
5 (Radiator)
6 (Baseboard)
B2
Terminal Unit
The time that the actuating motor requires to
operate from fully closed to fully open.
30 to 230 seconds
(1 sec. increments)
A
Motor Speed