Adjust Menu (1 of 2)
Section
Installer
Advanced
Range
Actual
Setting
DescriptionDisplay
B2
The desired room air temperature during an
occupied (Day) period.
(OUTDR DSGN ≠ OFF)
35 to 100°F
(2 to 38°C)
The desired room air temperature during an
unoccupied (Night) period.
(OUTDR DSGN ≠ OFF)
35 to 100°F
(2 to 38°C)
B2
Mixing setpoint temperature.
(OUTDR DSGN = OFF)
60 to 200°F
(16 to 93°C)
B2
The design outdoor air temperature used in the
heat loss calculation for the heating system. For
setpoint operation, set the OUTDR DSGN to OFF
-60 to 32°, OFF
(-51 to 0°C, OFF)
B2
The design indoor air temperature used in the
heat loss calculation for the heating system.
(OUTDR DSGN ≠ OFF)
35 to 100°F
(2 to 38°C)
B3
The design supply water temperature used in
the heat loss calculation for the heating system.
(OUTDR DSGN ≠ OFF)
70 to 220°F
(21 to 104°C)
B3
The maximum supply water temperature for the
mixing system
(OUTDR DSGN ≠ OFF)
80 to 210°F
(27 to 99°C)
B3
The minimum supply temperature for the
mixing system.
(OUTDR DSGN ≠ OFF)
OFF, 35 to 150°F
(OFF, 2 to 65°C)
B3
The minimum temperature allowed for the boiler
target temperature.
(Boiler sensor is present)
OFF, 80 to 180°F
(OFF, 27 to 82°C)
C1
The type of terminal units that are being used
in the heating system.
(OUTDR DSGN ≠ OFF)
1 (High Ma
ss
Radiant
2 (Low Mass Radiant
3 (Fancoil)
4 (Fin-tube Convector
5 (Radiator)
6 (Baseboard)
B2
Terminal Unit
The time that the actuating motor requires to
operate from fully closed to fully open.
30 to 230 seconds
(1 sec. increments)
A
Motor Speed