14
Table 4 – Electrical Ratings
Model No.
Part No. Max. HP
AC Line
Voltage
(50/60 Hz)
Phase
(Ø)
Max.
AC Line
Current
(Amps AC)
Fuse or
Circuit
Breaker
Rating
(Amps)
Voltage
Range
(Volts AC)
Max. Load
Current
(Amps/Phase)
Motor
Horsepower
Selection
2
(Jumper J2)
Net Wt.
Gray White
1
HP kW lbs kg
KBAC-24D 9987 9988 1 0.75
115
1
14.4 20
0 - 208/230 3.6 1 3/4 1/2 1/4 1/8 5.9 2.7
208/230 8.1 15
KBAC-27D 9520 9521
1½ 1.13 115
1
22 25
0 - 208/230
5.5 –
1½
3
1 3/4 1/2 10.3 4.7
2 1.5 208/230 16.7 20 6.7 2
3
A B C D E
KBAC-29 (1P)
4
10001 10002 3 2.25 208/230 1 20.5 25 0 - 208/230 9 3 2 1½ 1 3/4
10.3 4.7
KBAC-29 9528 9529
2 1.5
208/230
1 16.7 20
0 - 208/230
6.7 –
2
5
1½ 1 3/4
3 2.25 3 11.7 15 9 3
5
KBAC-45
6
9530 9531 3 2.25 400/460 3 7.2 10 0 – 400/460 5.5 3 2 1½ 1 3/4
KBAC-48
6
9540 9541 5 3.75 400/460 3 11 15 0 – 400/460 8.3 5 3 2 1½ 1
A B C
KBAC-217 8868 8879
5 3.75 208/230 3 22.1 25 0 - 208/230 17 5 3 2
22 10
KBAC-217S 8863 8855
KBAC-217F 8861 8853
KBAC-217SF 8869 8880
KBAC-416 8870 8881
10 7.5 400/460 3 20.8 25 0 – 400/460 16 10 7.5 5
KBAC-416S 8864 8856
KBAC-416F 8874 8883
KBAC-416SF 8871 8882
Notes: 1. White FDA approved nish. 2. Bold indicates factory setting. On Model KBAC-24D, Jumper J2 is labeled “1”, “3/4”, “1/2”, “1/4”, “1/8” (factory set to the
“1” position).On Model KBAC-27D, Jumper J2 is labeled “2”, “1½”, “1”, “3/4”, “1/2” (factory set to the “1½” position). On Models KBAC-29, 45, 48, Jumper J2 is
labeled “A”, “B”, “C”, “D”, “E” (factory set according to the table). 3. Model KBAC-27D is rated 1½ HP maximum with 115 Volt AC Line input and 2 HP maximum
with 208/230 Volt AC Line input. 4. Model KBAC-29 (1P) is rated 9 Amps at 35 °C / 95 °F and derated to 8.3 Amps at 40 °C / 104 °F. For ambient temperatures
above 40 °C / 104 °F, the drive is derated 2.5% per °C. 5. Model KBAC-29 is rated 2 HP maximum with single-phase AC Line input and 3 HP maximum with
3-phase AC Line input. 6. Models KBAC-45, 48, KBAC-217 Series and KBAC-416 Series are rated 0 – 400 Volts AC for 50 Hz motor operation and 0 – 460 Volts
AC for 60 Hz motor operation.