Setpoints - Advanced Menu
Setpoints - Advanced Menu
DEMAND DEFROST
Setpoints - Advanced Menu
SCHEDULE DEFROST
Setpoints - Advanced Menu
SCHEDULE DEFROST
w. CUSTOM DEFROST
PER DAY
Description Minimum Default Maximum
tS tS tS Temperature Setpoint -50°F 0°F 100°F
dtyP dtyP dtyP Type of Defrost, Air or Electric Air ELEc ELEc
dFit dFit dFit Defrost Initiation Mode dEnd dEnd ScHd
dPd dPd Defrost Per Day 0 4 12, CUS
dFt dFt Defrost Time 0 min 45 min 720 min
diF diF diF Temperature Dierential 30°
OFFt OFFt OFFt Minimum Compressor Otime 0 min 5 min 10 min
rUnt rUnt rUnt Minimum Compressor Runtime 0 min 2 min 10 min
FrEF FrEF FrEF
Fan mode during refrigeration
mode - ti24, OnCP, PErn
PErn OnCP ti24
AU1 AU1 AU1
Type of 1st Auxiliary input -diS,
COiL, rtP,SyOf, dOOr, t2nd, trdF,
indF, dFin, dFLO
COiL
StA1 StA1 StA1
Digital input active state for 1st
Aux input
OPEn SHrt SHrt
AU2 AU2 AU2
Type of 2nd Auxiliary input -diS,
COiL, rtP,SyOf, dOOr, t2nd, trdF,
indF, dFin, dFLO
diS
StA2 StA2 StA2
Digital input active state for 2nd
Aux input
OPEn SHrt SHrt
tS2 tS2 tS2 2nd room temp setpoint -50 -50 100
tOd Time of day 0:00 12:00 23:59, diS
d1 Start time of Defrost #1 0:00 diS 23:59, diS
d2 Start time of Defrost #2 0:00 diS 23:59, diS
d3 Start time of Defrost #3 0:00 diS 23:59, diS
d4 Start time of Defrost #4 0:00 diS 23:59, diS
d5 Start time of Defrost #5 0:00 diS 23:59, diS
d6 Start time of Defrost #6 0:00 diS 23:59, diS
d7 Start time of Defrost #7 0:00 diS 23:59, diS
d8 Start time of Defrost #8 0:00 diS 23:59, diS
d9 Start time of Defrost #9 0:00 diS 23:59, diS
d10 Start time of Defrost #10 0:00 diS 23:59, diS
d11 Start time of Defrost #11 0:00 diS 23:59, diS
d12 Start time of Defrost #12 0:00 diS 23:59, diS
dPtr Defrost Parameter 0
30 if ELEc
40 if Air
90
HEtr Heater Mode - Permanent or Pulse Pern
PuLS if ELEc
Pern if Air
PuLS
EdiF Extreme Dierential 0 20 200
dtSP dtSP dtSP
Defrost Term Temperature
Setpoint
35°F
50°F if ELEc
40°F if Air
90°F if ELEc
89.9°F if Air
drnt drnt drnt Drain Time 0 min 2 min 15 min
FdSP FdSP FdSP Fan delay temp -40°F
20°F if Elec
35°F if Air
35°F
Fndt Fndt Fndt Max fan delay time 0 min 2 min 20 min
FndF FndF FndF Fan State During Defrost OFF
OFF if Elec;
On if Air
On
Pdt Pdt Pdt Defrost pump down time 0 min 0 min 10 min
HAO HAO HAO High Alarm Oset
10° if tS <32
3° if tS >32
50°
LAO LAO LAO Low Alarm Oset 10°
tAd tAd tAd Temp Alarm Delay 1 min 60 min 180 min
Adr Adr Adr Modbus address 1 1 247
Unt Unt Unt Temp units FAH or CEL FAH FAH CEL
CLAL CLAL CLAL Not a setpoint, press “Enter” and hold until display changes. All Alarms Cleared