KE2 Temp + Defrost (pn 20611)
For Medium Temperature Applications with Air Defrost
Installation Manual
© Copyright 2016 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Basic Setpoints
Setpoint Description Minimum Default Maximum
tS Temperature Setpoint -50°F (-45°C) 35°F 100°F (38°C)
diF Dierential 1°F (1K) 2°F 30°F (17K)
CSH Maximum Compressor Starts/Hour 5 (O)* 6 10
dPd Defrost Per Day 0 6 12, CUS**
dFt Defrost Time 0 min 15 min 720 min
HAO High Alarm Oset 1°F (1K) 5°F 10°F (6K)
LAO Low Alarm Oset 1°F (1K) 3°F 10°F (6K)
tAd Temp Alarm Delay 1 min 90 min 180 min
Adr Mod Bus Address 1 1 247
Unt Units for temp display FAH FAH CEL
*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned o. The compressor will then function on
temperature only.
** Selecting CUS (custom) unlocks additional Setpoints. See Advanced Setpoints table.
Advanced Setpoints - includes setpoints only visible when CUS (custom) is selected under dPd (defrosts per day)
Setpoint Description Minimum Default Maximum
tS Temperature Setpoint -50°F (-45°C) 35°F 100°F (38°C)
diF Dierential 1°F (1K) 2°F 30°F (17K)
CSH Maximum Compressor Starts/Hour 5 (O)* 6 10
dPd Defrost Per Day 0 6 12, CUS
d12 Start time of Defrost #12 00 dis (disabled) 23,dis (disabled)
d11 Start time of Defrost #11 00 dis 23,dis
d10 Start time of Defrost #10 00 dis 23,dis
d9 Start time of Defrost #9 00 dis 23,dis
d8 Start time of Defrost #8 00 dis 23,dis
d7 Start time of Defrost #7 00 dis 23,dis
d6 Start time of Defrost #6 00 dis 23,dis
d5 Start time of Defrost #5 00 dis 23,dis
d4 Start time of Defrost #4 00 dis 23,dis
d3 Start time of Defrost #3 00 dis 23,dis
d2 Start time of Defrost #2 00 dis 23,dis
d1 Start time of Defrost #1 00 dis 23,dis
tod Time of Day 0.0 12.0 23.5
dFt
Defrost Time 0 min 15 min 720 min
HAO
High Alarm Oset 1°F (1K) 5°F 10°F (6K)
LAO
Low Alarm Oset 1°F (1K) 3°F 10°F (6K)
tAd
Temp Alarm Delay 1 min 90 min 180 min
Adr
Mod Bus Address 1 1 247
Unt
Units for temp display FAH FAH CEL
*Selecting fewer than 5 compressor starts per hour results in the starts per hour feature being turned o. The compressor will then function on
temperature only.
See page 7 for detailed Custom Defrost setup instructions
**CUS - Setpoints display when CUS selected