5. TECHNICAL SPECIFICATIONS
Model Capacity
(m³/h)
Connection
Size
Voltage Total
Installed
Power
(kw)
Nominal
Operting
(Amp)
MCA
(A)
Total
LRA
(A)
Fuse
(Amp)
***
Amount of
Refrigerant
(gr)
Refrigerant
gas
Pressure
drop
(mbar)
KRAD 15M 30 1/2" 230V / 1 / 50 Hz 0,34 1,72 2,10 8,85 4 300
R513a
150
KRAD 25M 42 1/2" 230V / 1 / 50 Hz 0,37 1,87 2,40 9,35 4 320
R513a
250
KRAD 40M 66 3/4" 230V / 1 / 50 Hz 0,39 1,87 2,35 9,75 4 500
R513a
90
KRAD 60M 96 3/4" 230V / 1 / 50 Hz 0,59 3,22 3,98 14,05 4 550
R513a
195
KRAD 80M 130 3/4" 230V / 1 / 50 Hz 0,68 3,83 4,73 18,65 6 600
R513a
285
KRAD 100M 168 1 1/2" 230V / 1 / 50 Hz 0,82 4,63 5,85 19,85 6 1000
R513a
195
KRAD 125M 240 1 1/2" 230V / 1 / 50 Hz 1,07 6,38 7,98 28,85 8 1000
R513a
285
KRAD 150M 300 1 1/2" 230V / 1 / 50 Hz 1,19 5,46 7,23 30,85 8 1000
R513a
175
KRAD 200M 396 2" 230V / 1 / 50 Hz 1,23 5,39 6,98 30,6 8
2500
R513a
275
KRAD 250M 498 2" 230V / 1 / 50 Hz 1,32 6,28 7,85 36,6 8 2500
R513a
215
*** Will be provided by the user
Note: Electrical protection class according to IEC is IP 54
FOR AIR COOLED MODELS
Nominal Working Pressure 7 barg
Maximum Working Pressure 16 barg
Maximum Ambient Temperature 50°C
Minimum Ambient Temperature 4°C
Maximum Inlet Temperature 60°C
FOR WATER COOLED MODELS
Maximum Working Pressure 16 barg
Maximum Water Temperature 30°C
Maximum Water Inlet Temperature 60°C
Minimum Water Temperature 5°C
Maximum Water Pressure 6 barg
Minimum Water Pressure 4 barg