Page 22
6.2 KRAD M
ELECTRICAL DIAGRAMS
With Control & Power
“User must supply the protective earth conductor of the dryer. The conductor is to be connected to
the point on the conducting body of the dryer, specified by a sticker with the protective earth symbol
next to it. The size of the protective earth conductor should be minimum the size of the power
conductor, minimum 16 mm² for power conductor size between 16 and 35 mm², minimum half the
size of the conductor if it is larger than 35 mm².