Electrical connection (non-Canada) - 3 wire cord
3-wire receptacle
(NEMA type 10-30R)
Internal ground
(GREEN screw)
Install
UL-approved
strain relief here
Terminal screw
recovery slot
Line 1
(BRASS terminal)
Neutral
(SILVER terminal)
Line 2
(BRASS terminal)
Access cover
screw
Terminal
block
Neutral
(center wire)
30 AMP
NEMA 10-30
DO NOT remove
internal ground in
a 3-wire system!!
Neutral
terminal
1 Turn off power supply to outlet.
2 Remove the screw securing the terminal block access
cover in the lower corner on the back of the dryer.
3 Install a UL-approved strain relief according to the
power cord/strain relief manufacturer’s instructions
in the power cord entry hole below the access panel.
At this time, the strain relief should be loosely in
place.
4 Thread an UNPLUGGED, UL-approved, 30 amp.
power cord, NEMA 10-30 type SRDT, through the
strain relief.
5 Attach the power cord neutral (center wire)
conductor to the SILVER colored center terminal on
the terminal block. Tighten the screw securely.
6 Attach the remaining two power cord outer
conductors to the outer, BRASS colored terminals on
the terminal block. Tighten both screws securely.
7 Follow manufacturer’s guidelines for fi rmly securing
the strain relief and power cord.
8 Reinstall the terminal block cover.
WARNING
ELECTRICAL SHOCK HAZARD
• Do not make a sharp bend or crimp wiring/conductor
at connections.
• DO NOT remove the internal ground from the GREEN
screw next to the terminal block.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to disconnect power source before servicing
could result in personal injury or even death.
IMPORTANT
If moving dryer from a 4-wire system and installing it
in a 3-wire system, move the internal ground from the
center terminal back to the GREEN screw next to the
terminal block.
NOTE
If a terminal screw falls during cord installation, it can
be retrieved in the terminal screw recovery slot below
the access panel.
Installation Instructions