K4C COMPACT-MULTI INSTALLATION/OPERATION MANUAL
K4C Compact-multi Feb-06
10
4.0 COMFORT ADJUSTMENTS
?? Outlet air is initially too warm or too cold - adjust the “FAN ON” setting.
?? Outlet air consistently too warm or too cold - change the blower motor speed to
give the specified air temperature rise (70 - 85°F).
?? Blower motor shuts off and the oil burner keeps going - the “FAN ON” setting is
set too low or the inlet air is below 50°F.
?? Outlet air gets too warm and burner shuts down - increase air by changing the
blower motor speed to give the specified temperature rise (70 - 85°F).
?? Outlet air is too warm or too cold at the end of the heating cycle after the burner
has turned off - adjust the “FAN OFF” time higher or lower.
5.0 REGULAR MAINTENANCE & CLEANING
Check complete operation at least once a year. In Canada see B139, Section 14,
Maintenance, for recommended servicing procedure. Heat exchanger ducts are
accessed through breech access panel at front of unit. Replace stainless steel gas
baffles after cleaning. Cerafelt (1/4”) gaskets may have to be replaced.