30
EN
6 - FURTHER DETAILS
If necessary, users may select the ADVANCED SETTINGS, which
allow modication of the control unit’s advanced parameters.
Proceed as follows:
CAUTION: the parameters may vary with respect to those in the table
below, depending on the motor to be installed.
6.1 - Customising the system - Advanced settings
14A
ADVANCED
SETTINGS
PARAMETERS DESCRIPTION DEFAULT MIN. MAX. UNIT
1 PHOTO 1
Use of PHOTO1 when starting from closed
0 = PHOTO 1 deactivated
1 = PHOTO1 is checked
2 = the gate starts even with PHOTO1 activated
2 0 2
2 PHOTO 2
Use of PHOTO2
0 = PHOTO 2 deactivated
1 = enabled during both opening and closing
OP/CL
2 =only enabled during opening OP
1 0 2
3 PHOTOTEST
Photo-device test
0 = o󰀨
1 = PHOTO1 on
2 = PHOTO2 on
3 = PHOTO1 and PHOTO2 on
0 0 3
4 EDGE TYPE
Sensitive edge type
0 = o󰀨
1 = 8k2 sensitive edge
2 = NC contact
3 = double sensitive edge 8k2 in parallel
1 0 3
5 SAFETY EDGE
Sensitive edge tripping mode
0 = only tripped during closure with direction
reversal*
1 = stops the automation during both opening
and closure and retreats from the obstacle with
short direction reversal
0 0 1
6
PARCIAL
OPENING LENGHT
Parcial opening 50 30 100
% (step
of 1)
7
AUTOMATIC
CLOSING FROM
PARCIAL OPEN
Time for automatic closure from parcial opening
(0=o󰀨)
1 to 900 Seconds of delay before automatic
closure from parcial opening
0 0 900 s
8 FLASH LIGHT
Flashing light output setup
0 = Fix
1 = Flashing
1 0 1
9 PRE-FLASHING Pre-ashing time (0 = o󰀨) 0 0 20 s
10
COURTESY LIGHT
START
Courtesy light setup
0 = ON at end of operation for courtesy light
time
1 = ON if gate not closed + courtesy light
duration time at end of operation
2 = ON if courtesy light timer has not gone out
since start of operation
0 0 2
11
COURTESY LIGHT
TIME
Courtesy light duration time (0 = o󰀨) 30 0 900 s
12
LIGHT
INTENSIVITY
AT END OF
MOVEMENT
0 = light o󰀨 after operation
5 = maximum brightness with motor stopped
2 0 5
13
STOP /
SAFETY EDGE
0 = NC stop button not connected
1 = NC stop button connected
2 = NC contact**
3 = 8k2 sensitive edge**
4 = double sensitive edge 8k2 in parallel**
1 0 4
* If the parameter is set to “0”, the intervention will be with brief reversal of motion on sliding gates and total reversal on swing gates.
** To activate PARAMETER No. 13, PARAMETER No. 5 (Sensitive Edge) must be set to “0”. If active, the EDGE input will only activate
on closing and the STOP input will only activate on opening, always with a short reversal of motion.