PARAMETERS DESCRIPTION DEFAULT MIN. MAX. UNIT
14 DEAD MAN
0 = o󰀨
1 = on (safety devices disabled)
0 0 1
15
GATE OPEN
INDICATOR
0 = deactivated
1 = gate open light ON/OFF
2 = gate open light proportional
3 = electric lock for partial gate ***
4 = electric lock for partial gate with relay
interface ****
5 = Tra󰀩c light When open COM/IND activated
and COM/ELEC deactivated (GREEN)
Not open COM/IND deactivated and COM/ELEC
activated (RED)
0 0 5
16 MAINTENANCE Service interval cycle threshold 10 1 200
x 1000
cycles
17
MAINTENANCE
FLASH
Enabling of continuous ashing when service is
required (only active with gate closed).
0 = o󰀨
1 = on
0 0 1
18
ELECTROLOCK
ACTIVATION
0 = magnetic electrolock. Output works only
when the gate is closed. We recommend to set
the pre-ash to 2 seconds ******
Activated for from 1 to 20 seconds when the
motors start to open the gate
2 0 20 s
19
WATER
HAMMERING IN
OPENING
From motor M1 closed
0 = o󰀨
Motor M1 activated for from 1 to 30 seconds in
the closing direction to ensure that the electric
lock releases
0 0 30 s
20
WATER
HAMMERING IN
CLOSING
From motor M1 closed
0 = o󰀨
Motor M1 activated for from 1 to 30 seconds in
the closing direction to ensure that the electric
lock engages
0 0 30 s
21
MOTOR RELEASE
AT STOP
Motor release from limit switch. Useful for
lightweight gates
0 = o󰀨
1 to 10 release levels (1 = minimum release, 10
= maximum release)
0 ***** 0 10
22
START UP BOOST
(NO FASTLINE)
High-speed motor start-up. Useful for heavy
gates in winter
0 = o󰀨
1 = on
2 = maximum
0 0 2
23
CLOSING DELAY
M 1
Leaf 1 closing delay with gate open
0 = O󰀨
1 = 1 to 180 Seconds On
1 0 180 s
24
ENCODER
(NO FASTLINE)
1 = O󰀨 (use of virtual encoder)
2 = On (use of motors physical encoder)
1 1 2
25
ENCODER
PULSES
(NO FASTLINE)
1 to 10 pulses per revolution of the physical
encoder (only with 24 set as “2”)
1 1 10
26
CIRCUIT BOARD
INPUT LOCKING
0 = Circuit board inputs active
1 = SBS-CLOSE-OPEN-PAR circuit board
inputs deactivated
WARNING! If the parameter is set as 1, the
control unit will request a 4-gure numerical
password, which will have to be entered again
to return the parameter to 0
0 0 1
27 DEFAULT Restoring the default values 0 0 1
*** The OPEN command from the transmitter and the 14A control unit will activate the parcial gate electric lock when the parameter is set on 3
or 4. The activation time is as set in parameter 18
**** If the setting is 4, the GATE OPEN WARNING LIGHT output must be connected to the coil of a relay (24 Vdc coil). Interface the relay contact
with the electric lock
***** For RÉVO motors, DEFAULT = 2
****** Gate closed = output activated; Gate not closed = output deactivated