CAUTION: BEFORE USING THE ALARM HUSH FEATURE, 
IDENTIFY THE SOURCE OF THE SMOKE AND BE CERTAIN 
A SAFE CONDITION EXISTS.
LED INDICATORS: This smoke alarm is equipped with red and green 
LED indicators. The red LED is located under the test button and has 
two modes of operation.
Standby Condition:  The red LED will flash every 30-40 
    seconds to indicate that the smoke 
    alarm is operating properly.
Alarm Condition:  When the alarm senses products of 
    combustion and goes into alarm, the red 
    LED will flash rapidly (one flash per second). 
    The rapid flashing LED and pulsating alarm 
    will continue until the air is cleared.
Hush Condition:  The red LED will flash every 10 seconds 
    as long as the alarm is in Hush mode.
SMOKE SENSING CHAMBER OPERATION: This alarm will “chirp” if 
any of the components in the smoke sensing chamber fail. This chirp 
will occur between the flashes of the red LED indicator light. (If the 
chirp occurs at the same time as the red LED flash, see section 6 for 
low battery information).
WHEN UNITS ARE INTERCONNECTED, only the red LED of the alarm 
which senses the smoke or is being tested (the originating unit) will 
flash rapidly. All other units in the interconnect system will sound an 
alarm but their red LED’s will NOT flash rapidly.
The green LED will be steady on to indicate the presence of AC power.
TESTING: Test by pushing the test button on the cover and holding it 
down for a minimum of 5 seconds.  This will sound the alarm if the 
electronic circuitry, horn, and battery are working.  In an intercon-
nected installation all interconnected alarms should sound when the 
test button on any one of the interconnected alarm is pressed.  If no 
alarm sounds, check the fuse or circuit breaker supplying power to 
the alarm circuit. Verify the green LED is on. If the alarm still does 
not sound, the unit has defective batteries or other failure. DO NOT 
use an open flame to test your alarm, you could damage the alarm 
or ignite combustible materials and start a structure fire.
TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION. Erratic 
or low sound coming from your alarm may indicate a defective 
alarm, and it should be returned for service (see section 12).
NOTE:  WEEKLY TESTING IS REQUIRED.
1375-7213-00(21008164-EN A).indd   91375-7213-00(21008164-EN A).indd   9 2010.10.7   2:06:25 PM2010.10.7   2:06:25 PM