Chapter 5: Installation
P/N 3101890-EN • REV 006 • ISS 21JUN18 87
Mount the GSA-CC1 and GSA-CT1 inside the booster supply cabinet as described in the technical documentation
received with booster supply. Connect field wiring as shown in Figure 28 on page 88.
Booster power supply configuration
Set DIP switches SW 2-6 to On. This configures the booster supply’s trouble relay to close only on loss of AC
power. All other booster troubles are signaled through the sense circuits.
Note: In Figure 28, the booster supply is configured so that Sense 1 controls all four NACs. For DIP switch
settings for this and other booster supply configurations see the technical documentation received with the
booster supply.
GSA modules configuration
Configure the GSA-CC1 and GSA-CT1 modules as shown in the table below.
Table 29: GSA-CC1 and GSA-CT1 configuration settings
Properties
-CC1 Device Type = COMMONALARMOUTPUT
Personality = (5) Signal -
supervised output (Class B)
Text 1 = REMOTE_SUPPLY
Text 2 = SENSE_1
-CT1 Model = CT1
Device Type = ACFAIL
Personality = (3) Active - NO nonlatching (Class B)
Text 1 = REMOTE_SUPPLY
Text 2 = AC_FAILURE