1.3 Environmental Condition
Kinco-KS accords with GB/T 15969.3-2007idt IEC61131-22007standard and test
specifications.
The following table lists the conditions and requirements for Kinco-KS to work properly. It
is the user's responsibility to ensure that the service conditions are not exceeded.
Transport and storage
temperature
-40 --- +70 °C
relative
humidity
10%~95%, no condensation
Altitude
Up to 3000 m
Free falls
With manufacturer's original packaging, 5 falls from 1m
of height.
Normal Operation
Ambient
conditions
air
temperature
Open equipment : -10 --- +55°C; Enclosed equipment: -10
--- +40°C
relative
humidity
10%~95%, no condensation
Altitude
Up to 2000 m
Pollution
degree
for use in pollution degree 2.
Mechanical
conditions
Sinusoidal
vibrations
5<f<8.4Hz, Occasional: 3.5mm amplitude; Continuous:
1.75mm mplitude.
8.4<f<150, Occasional: 1.0g acceleration; Continuous:
0.5g acceleration.
Shock
occasional excursions to 15g, 11 ms, half-sine, in each of 3
mutually perpendicular axes.
Electromagnet
ic
Electrostatic
discharge
±4kV Contact, ±8kV Air. Performance criteria B.