Device weights:
MODEL
Weight
net
net
net
ESSENTIAL-100
45 kg
52 kg
+ 5 kg
ESSENTIAL-280
73kg
85 kg
+ 7 kg
ESSENTIAL-460
109 kg
122kg
+ 10 kg
ESSENTIAL-700
146 kg
174 kg
+ 20 kg
Commissioning and operation
Do not commission a device that has been damaged during transport or set-up. If in doubt, contact the supplier.
Do not damage parts of the refrigerant circuit. If the evaporator pipes are pierced by a sharp object, other pipes
become kinked, or the surface finish is scratched off, refrigerant spraying out can cause eye injuries.
Connecting the device
o The electrical connection conditions must match those stated on the type plate of the refrigerating
machine.
o KIRSCH refrigerating machines and freezers are ready-to-plug-in devices, operate at 220-240 volts
and at 50 or 60 Hz alternating current, depending on the model. Special designs that deviate from
these specifications are available; refer to the type plate in the upper right of the interior!
o Connect the device using a correctly installed plug with an earth connection.
o Fuse: 10 amp.
o KIRSCH refrigerating machines and freezers are designed according to protection class I.
Cleaning
o Clean the interior and exterior of the device before commissioning and at regular intervals thereafter.
o Before you clean the device, switch it off and pull out the mains plug.
o Cleaning water must not enter the electrical components.
o Clean the interior container and equipment with warm water and some mild detergent. Cleaning
agents containing sand or acid, or chemical solutions are unsuitable.
o Wipe down the door seal with clear water and rub this dry thoroughly.
o You can remove drawers and wire shelves for cleaning.
o Treat white-coated exterior housing with a paint cleaner and care product. Treat stainless-steel ex-
terior housing with a stainless-steel cleaner and care product.
o To ensure that the refrigerating machine's performance is not affected by dust, clean the condenser
with a brush or vacuum cleaner as appropriate according to the build-up of dust but at least every 6
months. The condenser is a black wire part, located on the external back wall or in the motor area,
depending on the model.
Maintenance
o KIRSCH refrigerating machines and freezers are maintenance-free.
o However, observe the prior section entitled "Cleaning".