  • G
    Gregory FosterAug 19, 2025
    How to fix 111 HP warning on KKT chillers Chiller?
    • A
      alan07Aug 19, 2025
      The 111 HP warning on your KKT chillers Chiller usually indicates a condensation pressure issue. Start by cleaning the condenser and filter. Also, inspect the fan, cooling water circuit, and ensure the cover panels are installed.
  • M
    Michael HarrisAug 21, 2025
    What to do if KKT chillers Chiller shows 151 HP STOP?
    • A
      Ashley KaiserAug 21, 2025
      The 151 HP STOP error on your KKT chillers Chiller indicates that the condensation pressure is outside the allowable range. To resolve this, begin by cleaning the condenser and filter. Additionally, verify the fan's functionality, inspect the cooling water circuit, and ensure the cover panels are properly installed.
  • M
    Michael GonzalezAug 23, 2025
    Why is my KKT chillers cBoxX 40 showing a 121 LP warning?
    • K
      katherinetaylorAug 23, 2025
      The 121 LP warning on your KKT chillers Chiller is related to evaporation pressure. Begin by checking the liquid flow. Also, check the function of the expansion valve and verify the refrigerant level.
  • J
    james80Aug 26, 2025
    What to do for '304 Temp. cooling water On Max Warn' in KKT chillers cBoxX 40?
    • R
      Robin FisherAug 26, 2025
      If your KKT chillers Chiller displays a '304 Temp. cooling water On Max Warn' message, it means the cooling water circuit isn't working or no cooling water is being supplied. You should check the cooling water generation and the cooling water circuit.
  • V
    Valerie SmithAug 27, 2025
    How to solve '321 Coldwater press warning' on KKT chillers cBoxX 40 Chiller?
    • L
      lkeyAug 27, 2025
      If your KKT chillers Chiller shows '321 Coldwater press warning', it could be due to a closed external slide, a soiled filter, or air in the system. Open the external slide valve, clean the filter, and vent the system to resolve this.
  • M
    Monica ZamoraAug 29, 2025
    What does '386 Pump pressure 2 Min STOP' mean on KKT chillers cBoxX 40?
    • A
      Amanda LawrenceAug 30, 2025
      The '386 Pump pressure 2 Min STOP' error on your KKT chillers Chiller is caused by a flow rate that's too high, chiller resistance that's too low, or air in the system. Reduce the flow rate, increase the chiller resistance, and vent the system.
  • B
    brandonbuchananAug 31, 2025
    How do I troubleshoot '326 Press pump 1 min' on KKT chillers Chiller?
    • N
      Nathan BoydSep 1, 2025
      The '326 Press pump 1 min' warning on your KKT chillers Chiller is caused by a flow rate that is too high, chiller resistance that is too low, or air in the system. Reduce the flow rate, increase the chiller resistance, and vent the system.
  • A
    Anita ReyesSep 3, 2025
    What does '602 DI phase monitoring' mean on KKT chillers Chiller?
    • G
      gabriel45Sep 3, 2025
      The error '602 DI phase monitoring' on your KKT chillers Chiller indicates an issue with the phase sequence, a phase failure, undervoltage, or asymmetry. Check the feed.
  • D
    Dawn LarsonSep 5, 2025
    What causes '301 Outlettemp. 1 max warning' on KKT chillers Chiller?
    • L
      leslie58Sep 5, 2025
      If your KKT chillers Chiller displays a '301 Outlettemp. 1 max warning', it's likely due to thermal overload or a lack of refrigeration. Check the refrigerating capacity and the function of the refrigeration circuit.
  • C
    Christine SteeleSep 7, 2025
    What to do if KKT chillers cBoxX 40 Chiller shows 123 Compr.Pump Out Warn?
    • J
      Jeremy StevensSep 7, 2025
      The error '123 Compr.Pump Out Warn' on your KKT chillers Chiller is caused by the EEV not closing, MV hot gas bypass leaks, or a refrigerant circuit bypass. Check the EEV and check the MV hot gas circuit for leaks.