EasyManua.ls Logo

KKT chillers KSC Series - User Manual

Default Icon
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Operating Instruction
Healthcare chiller of the KSC Series
Type KPC 115-L-U/S
page 1
Manufacturer
ait-deutschland GmbH T +49 9228 9977 0
Industriestraße 3 F +49 9228 9977 149
95359 Kasendorf E info@kkt-chillers.com
Germany W www.kkt-chillers.com
Representative in the US and Service Center
KKT chillers, Inc. T 847 734 1600
1280 Landmeier Road F 847 734 1601
Elk Grove Village TF 866 517 6867
IL 60007 E support@kkt-chillersusa.com
YOUR LOCAL SERVICE CONTRACTOR IS:
COMPANY NAME:
PHONE NUMBER: FAX NUMBER:
\\FILER02\VOL1\SIEMENS MED\KPC 115 L\03_DOKUMENTE\B&W L-US\MANUAL_SN224_NEUER FREQUENZUMWANDLER\KKTCHILLERS_KPC115-L-U_S_224.DOC 83000301.K

Questions and Answers

  • R
    Richard BergerAug 15, 2025
    Why does my KKT Chiller refrigerating machine start and stop frequently?
    • A
      anthonyjohnAug 15, 2025
      If your KKT Chiller's refrigerating machine starts and stops frequently, it could be due to insufficient fresh air supply to the condenser, causing the high-pressure pressostat to protect the machine from overload. Ensure adequate fresh air supply and removal, and eliminate any short-circuit between fresh and exhaust air. Alternatively, there might be insufficient pressure in the refrigerant circuit due to a refrigerant leak. Locate the leak, seal it, and refill the circuit.
  • D
    davidsonjohnAug 18, 2025
    How to troubleshoot malfunction of plant/system in KKT Chiller?
    • E
      Elizabeth TorresAug 18, 2025
      If your KKT Chiller plant/system is malfunctioning, several causes could be responsible. It might be due to a power failure, so check the mains connection. Another possibility is a defective thermostat feeler; inspect the feeler by clamping it and measuring the resistance. Also, a feeler malfunction could be the cause. In this case, check the thermostat by bridging the feeler to see if the thermostat relay shuts and the compressor starts.
  • T
    troy13Aug 22, 2025
    Why KKT Chiller is not providing enough refrigeration power?
    • K
      Kristin SmithAug 22, 2025
      If your KKT Chiller isn't providing enough refrigeration power, there are several potential causes. You might have air in the water circuit, so vent the system. It's also possible that the water agitation quantity has fallen below the minimum; ensure the water pipe cross-section is correctly designed, open the check valve in the water circuit completely, or increase the pipe cross-section. Check for enough fresh air supply for condenser and eliminate any short-circuit across fresh air and exhaust air. Finally, there might not be enough refrigerant in the circuit; find the leak, seal it, and refill the circuit.
  • C
    Cynthia BlevinsAug 25, 2025
    What to do if KKT Chiller pump is malfunctioning?
    • D
      David RiveraAug 26, 2025
      If your KKT Chiller's pump is malfunctioning, first ensure the main switch is on and the control switch is set to 'AUTO'. Check for defective fuses, including the main fuse and the fuse for control current, and replace them if necessary. If the pump motor is defective, replace it. Also, verify the water quantity if the flow controller has responded. Finally, check for a shortage of water by inspecting the system pressure and cleaning the strainer.
  • R
    Raymond SanfordAug 28, 2025
    Why does my KKT Chiller compressor stop?
    • M
      Mary WatkinsAug 28, 2025
      If the compressor in your KKT Chiller stops, it could be due to a tripped Klixon/INT69. Allow the compressor to cool down, and consider cleaning the condenser or improving fresh air supply. If the Klixon/INT69 is defective, replace it.
  • J
    jamiehodgeSep 1, 2025
    What causes still malfunction of refrigerating machine in KKT Chiller?
    • O
      owensmariaSep 1, 2025
      If your KKT Chiller's refrigerating machine is still malfunctioning, it could be due to several reasons. Check for low pressure in the refrigerant circuit; find any leaks, seal them, and refill the circuit. A dirty dryer in the liquid pipe could also be the cause, so replace the dryer. Additionally, inspect the pressure relief valve and solenoid valve in the liquid pipe, replacing them if defective. High pressure in the refrigerant circuit might be the issue, so clean the condenser. If the fan is defective, identify and fix the electrical cause and check the fuses. High outside temperatures can also cause problems, so spray the condenser with water. Lastly, a defective pressostat for condenser control should be replaced.
  • L
    Lorraine ButlerSep 4, 2025
    What to do if still malfunction of pump in KKT Chiller?
    • J
      jeremywallaceSep 4, 2025
      If your KKT Chiller pump continues to malfunction, it could be due to an overload trip of the pump protection interrupting the control circuit. Set the main switch to '0' and push in the overload trip.
  • F
    Frank FordSep 7, 2025
    Why electrical heater in water circuit of KKT Chiller does not work?
    • J
      juliemooreSep 7, 2025
      If the electrical heater in your KKT Chiller's water circuit isn't working, it could be because the electrical heating box has exceeded 266°F (130°C), causing an automatic switch to break the contact. The reset (located under the heater cover) must be manually pressed. Also, control the pressure from the water circuit and prepare the cause of water lack and fill the water circuit, if necessary. Finally, control the Parameter of the temperature controller witch switches the heater and set the right Parameter in the temperature controller (which switches the electrical heater), if necessary.
  • A
    Andrew PopeSep 12, 2025
    Why does the KKT Chiller pump make a gurgling noise?
    • L
      Larry SmithSep 12, 2025
      If your KKT Chiller pump makes a gurgling noise, the circuit is likely not completely vented. Vent the system and fill it up with water/Ethylene glycol.