Questions and Answers

  • A
    Amy MeyerAug 19, 2025
    How to fix 111 HP warning on KKT chillers cBoxX 100?
    • R
      Ralph BrightAug 19, 2025
      The 111 HP warning on your KKT chillers Chiller usually indicates a condensation pressure issue. Start by cleaning the condenser and filter. Also, inspect the fan, cooling water circuit, and ensure the cover panels are installed.
  • D
    daniel68Aug 21, 2025
    What to do if KKT chillers cBoxX 100 shows 151 HP STOP?
    • D
      Dylan HarrisAug 21, 2025
      The 151 HP STOP error on your KKT chillers Chiller indicates that the condensation pressure is outside the allowable range. To resolve this, begin by cleaning the condenser and filter. Additionally, verify the fan's functionality, inspect the cooling water circuit, and ensure the cover panels are properly installed.
  • C
    Christopher JacksonAug 23, 2025
    Why is my KKT chillers cBoxX 100 showing a 121 LP warning?
    • G
      Gail BrockAug 25, 2025
      The 121 LP warning on your KKT chillers Chiller is related to evaporation pressure. Begin by checking the liquid flow. Also, check the function of the expansion valve and verify the refrigerant level.
  • M
    michelle52Aug 26, 2025
    What to do for '304 Temp. cooling water On Max Warn' in KKT chillers cBoxX 100 Chiller?
    • B
      Brad ChambersAug 26, 2025
      If your KKT chillers Chiller displays a '304 Temp. cooling water On Max Warn' message, it means the cooling water circuit isn't working or no cooling water is being supplied. You should check the cooling water generation and the cooling water circuit.
  • T
    Tracy LewisAug 28, 2025
    How to solve '321 Coldwater press warning' on KKT chillers cBoxX 100?
    • L
      Lindsay DiazAug 28, 2025
      If your KKT chillers Chiller shows '321 Coldwater press warning', it could be due to a closed external slide, a soiled filter, or air in the system. Open the external slide valve, clean the filter, and vent the system to resolve this.
  • E
    Elijah CarlsonAug 30, 2025
    What does '386 Pump pressure 2 Min STOP' mean on KKT chillers cBoxX 100?
    • M
      Maria FerrellAug 30, 2025
      The '386 Pump pressure 2 Min STOP' error on your KKT chillers Chiller is caused by a flow rate that's too high, chiller resistance that's too low, or air in the system. Reduce the flow rate, increase the chiller resistance, and vent the system.
  • A
    Alexandra EllisSep 1, 2025
    How do I troubleshoot '326 Press pump 1 min' on KKT chillers cBoxX 100?
    • S
      Spencer GriffinSep 1, 2025
      The '326 Press pump 1 min' warning on your KKT chillers Chiller is caused by a flow rate that is too high, chiller resistance that is too low, or air in the system. Reduce the flow rate, increase the chiller resistance, and vent the system.
  • R
    Robert CostaSep 3, 2025
    What does '602 DI phase monitoring' mean on KKT chillers cBoxX 100?
    • S
      Sabrina SharpSep 3, 2025
      The error '602 DI phase monitoring' on your KKT chillers Chiller indicates an issue with the phase sequence, a phase failure, undervoltage, or asymmetry. Check the feed.
  • J
    jasonjeffersonSep 5, 2025
    What causes '301 Outlettemp. 1 max warning' on KKT chillers cBoxX 100?
    • J
      Jeffrey LoganSep 6, 2025
      If your KKT chillers Chiller displays a '301 Outlettemp. 1 max warning', it's likely due to thermal overload or a lack of refrigeration. Check the refrigerating capacity and the function of the refrigeration circuit.
  • H
    heatherjamesSep 7, 2025
    What to do if KKT chillers cBoxX 100 shows 123 Compr.Pump Out Warn?
    • E
      Edwin HopkinsSep 8, 2025
      The error '123 Compr.Pump Out Warn' on your KKT chillers Chiller is caused by the EEV not closing, MV hot gas bypass leaks, or a refrigerant circuit bypass. Check the EEV and check the MV hot gas circuit for leaks.

Summary

Product Description

Technical Data

Provides detailed specifications and performance parameters of the chiller.

Function and Main Components

Control Unit; Main Circuit Board

Explains the central control unit that manages all system functions.

Safety

Hazard Warnings

Explains the importance and meaning of warning labels on the machine.

Installation

Installation Site

Details requirements and considerations for choosing an installation location.

Hydraulic Installation

Guides the proper connection of hydraulic lines to the chiller.

Electrical Installation

Provides instructions for the safe and correct electrical installation.

Commissioning

Operation

Selecting the Operating Mode

Explains the different operating modes (STANDBY, AUTO, ON).

Control Panel

Describes the physical control panel elements and their functions.

Settings

Describes how to adjust setpoints, parameters, and times.

Alarm Menu

Explains how to view, acknowledge, and interpret alarms.

Controller Description

Compressor Control

Details how compressors are managed based on load and faults.

Cleaning

Service

Fault Correction

Directs users to resources for troubleshooting and correcting faults.

Troubleshooting

Maintenance Intervals in Accordance with the VDMA

KKT chillers cBoxX 100 Specifications

General IconGeneral
BrandKKT chillers
ModelcBoxX 100
CategoryChiller
LanguageEnglish

Related product manuals