NCVT-1XT RT210
ENGLISH
WARNINGS
To ensure safe operation and service of the tester, follow these instructions.
Failure to observe these warnings can result in severe injury or death.
Risk of electric shock and burn. Contact with live circuits could result in death or serious
injury.
Use caution with voltages above 25V AC as a shock hazard may exist.
injury.
Use caution with voltages above 25V AC as a shock hazard may exist.
injury.
A blinking LED or a steadily illuminated LED in the tip and audible beeps indicate presence
Use caution with voltages above 25V AC as a shock hazard may exist.
A blinking LED or a steadily illuminated LED in the tip and audible beeps indicate presence
Use caution with voltages above 25V AC as a shock hazard may exist.
of voltage. If no indication, voltage could still be present.
A blinking LED or a steadily illuminated LED in the tip and audible beeps indicate presence
of voltage. If no indication, voltage could still be present.
A blinking LED or a steadily illuminated LED in the tip and audible beeps indicate presence
Before and after each use, verify operation by testing a known working circuit that is within
of voltage. If no indication, voltage could still be present.
Before and after each use, verify operation by testing a known working circuit that is within
of voltage. If no indication, voltage could still be present.
the rating of this unit.
Before and after each use, verify operation by testing a known working circuit that is within
the rating of this unit.
Before and after each use, verify operation by testing a known working circuit that is within
Never assume neutral or ground wires are de-energized. Neutrals in multi-wire branch
the rating of this unit.
Never assume neutral or ground wires are de-energized. Neutrals in multi-wire branch
the rating of this unit.
circuits may be energized when disconnected and must be retested before handling.
Never assume neutral or ground wires are de-energized. Neutrals in multi-wire branch
circuits may be energized when disconnected and must be retested before handling.
Never assume neutral or ground wires are de-energized. Neutrals in multi-wire branch
The tester
circuits may be energized when disconnected and must be retested before handling.
The tester
circuits may be energized when disconnected and must be retested before handling.
WILL NOT
circuits may be energized when disconnected and must be retested before handling.
WILL NOT
circuits may be energized when disconnected and must be retested before handling.
detect voltage if:
circuits may be energized when disconnected and must be retested before handling.
detect voltage if:
circuits may be energized when disconnected and must be retested before handling.
WILL NOT detect voltage if:WILL NOT
circuits may be energized when disconnected and must be retested before handling.
WILL NOT
circuits may be energized when disconnected and must be retested before handling.
detect voltage if:
circuits may be energized when disconnected and must be retested before handling.
WILL NOT
circuits may be energized when disconnected and must be retested before handling.
The wire is shielded.
detect voltage if:
The wire is shielded.
detect voltage if:
The operator is not grounded or is otherwise isolated from an effective earth ground.
The voltage is DC.
The operator is not grounded or is otherwise isolated from an effective earth ground.
The voltage is DC.
The operator is not grounded or is otherwise isolated from an effective earth ground.
The tester
The voltage is DC.
The tester
The voltage is DC.
MAY NOT
The voltage is DC.
MAY NOT
The voltage is DC.
detect voltage if:
The user is not holding the tester.
detect voltage if:
The user is not holding the tester.
detect voltage if:
The user is insulated from the tester with a glove or other materials.
The user is not holding the tester.
The user is insulated from the tester with a glove or other materials.
The user is not holding the tester.
The wire is partially buried or in a grounded metal conduit.
The user is insulated from the tester with a glove or other materials.
The wire is partially buried or in a grounded metal conduit.
The user is insulated from the tester with a glove or other materials.
The tester is at a distance from the voltage source.
The wire is partially buried or in a grounded metal conduit.
The tester is at a distance from the voltage source.
The wire is partially buried or in a grounded metal conduit.
The field created by the voltage source is being blocked, dampened, or otherwise
The tester is at a distance from the voltage source.
The field created by the voltage source is being blocked, dampened, or otherwise
The tester is at a distance from the voltage source.
interfered with.
The field created by the voltage source is being blocked, dampened, or otherwise
interfered with.
The field created by the voltage source is being blocked, dampened, or otherwise
The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
The tester is outside of operating conditions (listed in Specifications section).
The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
The tester is outside of operating conditions (listed in Specifications section).
The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
Operation may be affected by differences in socket design and insulation thickness and
The tester is outside of operating conditions (listed in Specifications section).
Operation may be affected by differences in socket design and insulation thickness and
The tester is outside of operating conditions (listed in Specifications section).
type; tester may not be compatible with some types of standard or tamper resistant (TR)
Operation may be affected by differences in socket design and insulation thickness and
type; tester may not be compatible with some types of standard or tamper resistant (TR)
Operation may be affected by differences in socket design and insulation thickness and
electrical outlets.
type; tester may not be compatible with some types of standard or tamper resistant (TR)
electrical outlets.
type; tester may not be compatible with some types of standard or tamper resistant (TR)
In bright light conditions, the LED visual indicators will be less visible.
When powered-ON, one of the “power-ON” LED’s will be illuminated, and a green light
In bright light conditions, the LED visual indicators will be less visible.
When powered-ON, one of the “power-ON” LED’s will be illuminated, and a green light
In bright light conditions, the LED visual indicators will be less visible.
will illuminate the tip.
When powered-ON, one of the “power-ON” LED’s will be illuminated, and a green light
will illuminate the tip.
When powered-ON, one of the “power-ON” LED’s will be illuminated, and a green light
DO NOT USE TESTER UNLESS ONE OF THE “POWER-ON” LED
When powered-ON, one of the “power-ON” LED’s will be illuminated, and a green light
DO NOT USE TESTER UNLESS ONE OF THE “POWER-ON” LED
When powered-ON, one of the “power-ON” LED’s will be illuminated, and a green light
s
IS
ILLUMINATED.
will illuminate the tip.
ILLUMINATED.
will illuminate the tip.
Do not use if tester appears damaged or is not operating properly. If in doubt, replace the
tester.
Do not use if tester appears damaged or is not operating properly. If in doubt, replace the
tester.
Do not use if tester appears damaged or is not operating properly. If in doubt, replace the
Do not apply more than the rated voltage as marked on the tester (1000V).
Do not apply to uninsulated hazardous live conductors.
Do not apply more than the rated voltage as marked on the tester (1000V).
Do not apply to uninsulated hazardous live conductors.
Do not apply more than the rated voltage as marked on the tester (1000V).
Detection above 70V AC is specified under "normal" conditions as detailed below. The tester
may detect at a different threshold at different conditions, or may not detect at all unless:
Detection above 70V AC is specified under "normal" conditions as detailed below. The tester
may detect at a different threshold at different conditions, or may not detect at all unless:
Detection above 70V AC is specified under "normal" conditions as detailed below. The tester
The tip of the tester is within 0.25" (6 mm) of an AC voltage source radiating unimpeded.
may detect at a different threshold at different conditions, or may not detect at all unless:
The tip of the tester is within 0.25" (6 mm) of an AC voltage source radiating unimpeded.
may detect at a different threshold at different conditions, or may not detect at all unless:
The user is holding the body of the tester with his or her bare hand.
The tip of the tester is within 0.25" (6 mm) of an AC voltage source radiating unimpeded.
The user is holding the body of the tester with his or her bare hand.
The tip of the tester is within 0.25" (6 mm) of an AC voltage source radiating unimpeded.
The user is standing on or connected to earth ground.
The user is holding the body of the tester with his or her bare hand.
The user is standing on or connected to earth ground.
The user is holding the body of the tester with his or her bare hand.
The air humidity is nominal (50% relative humidity – non-condensing).
The user is standing on or connected to earth ground.
The air humidity is nominal (50% relative humidity – non-condensing).
The user is standing on or connected to earth ground.
The tester is held still.
The air humidity is nominal (50% relative humidity – non-condensing).
The tester is held still.
The air humidity is nominal (50% relative humidity – non-condensing).
Always wear approved eye protection.
Comply with local and national safety requirements.
Always wear approved eye protection.
Comply with local and national safety requirements.
Always wear approved eye protection.
If this product is used in a manner not specified by the manufacturer, protection provided
Comply with local and national safety requirements.
If this product is used in a manner not specified by the manufacturer, protection provided
Comply with local and national safety requirements.
by the product may be affected.
If this product is used in a manner not specified by the manufacturer, protection provided
by the product may be affected.
If this product is used in a manner not specified by the manufacturer, protection provided
OPERATING INSTRUCTIONS
CHECKING FOR THE PRESENCE OF AC VOLTAGE
1. Press the Power On / Off button. After performing a self-test,
a green LED
3
will illuminate the tip when no voltage is
detected.
2. Prior to use, test on a known live circuit to verify tester
functionality.
3. Place tip of the tester
4
near AC voltage. If voltage is present,
the unit will emit audible beeps and the red LED
3
in the tip
will illuminate.
SILENT OPERATION
To activate silent operation, power-ON by pressing and holding
the NCV Power-ON button
1
for more than 2 seconds. Power-
ON in this manner each time silent operation is desired.
CLEANING
Be sure tester is turned off and wipe with a clean, dry lint-
free cloth.
Do not use abrasive cleaners or solvents.
STORAGE
Remove the batteries when not in use for a prolonged period
of time. Do not expose to high temperatures or humidity. After
a period of storage in extreme conditions exceeding the limits
mentioned in the General Specifications section, allow the tester
to return to normal operating conditions before using.
FCC AND IC COMPLIANCE
See this product’s page at www.kleintools.com for FCC
compliance information.
Canada ICES-003 (B) / NMB-003 (B)
CUSTOMER SERVICE
KLEIN TOOLS, INC.
450 Bond Street, Lincolnshire, IL 60069 1-800-553-4676 customerservice@kleintools.com www.kleintools.com
MAINTENANCE
BATTERY REPLACEMENT
When the battery is low, the unit will power-on with a blinking red
LED
2
. When this happens, the batteries must be replaced:
1. Unscrew the battery cap
7
and remove/recycle spent
batteries.
2. Install two new AAA batteries. Note proper polarity.
3. Screw battery cap tightly to ensure a tight seal with the O-Ring
6
.
FUNCTION BUTTONS
NCV POWER ON/OFF BUTTON
1
Press and release the NCV Power button
1
. The tester will emit a
single beep, the Power On Indicator
2
and green LED
3
in the tip
will illuminate. To power-OFF the tester, press and release the Power
On / Off button
1
. The tester will emit a double beep.
NOTE: The tester will automatically power-OFF following 4
minutes of inactivity to conserve battery life.
CAUTION
DO NOT
attempt to repair this tester. It contains no serviceable parts.
DO NOT attempt to repair this tester. It contains no serviceable parts.DO NOT
DO NOT
attempt to repair this tester. It contains no serviceable parts.
DO NOT
attempt to repair this tester. It contains no serviceable parts.
expose tester to extremes in temperature or high humidity.
attempt to repair this tester. It contains no serviceable parts.
expose tester to extremes in temperature or high humidity.
attempt to repair this tester. It contains no serviceable parts.
DO NOT expose tester to extremes in temperature or high humidity.DO NOT
attempt to repair this tester. It contains no serviceable parts.
DO NOT
attempt to repair this tester. It contains no serviceable parts.
expose tester to extremes in temperature or high humidity.
attempt to repair this tester. It contains no serviceable parts.
DO NOT
attempt to repair this tester. It contains no serviceable parts.
GENERAL SPECIFICATIONS
The Klein Tools NCVT-1XT is a durable 70 to 1000V AC non-contact voltage tester
with IP67 rating and a 3m (9.8') drop protection.
Environment: Indoor
Measurement Range: 70 to 1000V AC
Frequency Range: 50 to 500 Hz
Batteries: 2x AAA 1.5V Alkaline
Operating and Storage Altitude: Up to 6562 ft. (2000 m)
Operating and Storage Temp: 14° to 122°F (-10° to 50°C)
Relative Humidity: <95% non-condensing
Dimensions: 5.34" x 1.08" x 0.97" (135.6 x 27.4 x 22.1 mm)
Weight: 1.65 oz (46.7 g) with batteries
Pollution degree: 2
Safety Rating: CAT IV 1000V AC
Drop Protection: 9.8 ft. (3 m)
Ingress Protection: IP67
Standards: EN 61010-1:2010+A1: 2019,
EN IEC 61010-2-030:2021+A11:2021.
Conforms to UL STD. 61010-1, 61010-2-030
Certi ed to CSA STD. C22.2 No. 61010-1, 61010-2-030.
Specifications subject to change.
GENERAL SPECIFICATIONS
Environment: Indoor
Operating and Storage Altitude: Up to 6562 ft. (2000 m)
Operating Temperature: 32° to 140°F (0° to 40°C)
Storage Temperature: 14° to 122°F (-10° to 50°C)
Relative Humidity: <85% non-condensing
Mains supply voltage  uctuations: ±10%
Nominal Voltage: 110 - 125V AC at 50/60Hz in 3-wire outlet
Standards: Conforms to UL Std 61010-1, 61010-2-030,1436.
Certi ed to
CSA Std C22.2 #61010-1, 61010-2-030,160
.
Specifications subject to change.
5001748
5001748
WARNINGS
Read, understand, and follow all warnings and instructions before operating testers. Failure to
follow instructions could result in death or serious injury. Before each use, verify tester operation
Read, understand, and follow all warnings and instructions before operating testers. Failure to
follow instructions could result in death or serious injury. Before each use, verify tester operation
Read, understand, and follow all warnings and instructions before operating testers. Failure to
by testing on a known live and correctly wired receptacle. Do not use if the tester appears
follow instructions could result in death or serious injury. Before each use, verify tester operation
by testing on a known live and correctly wired receptacle. Do not use if the tester appears
follow instructions could result in death or serious injury. Before each use, verify tester operation
damaged in any way. The tester is intended for indoor use only. Other equipment or devices
by testing on a known live and correctly wired receptacle. Do not use if the tester appears
damaged in any way. The tester is intended for indoor use only. Other equipment or devices
by testing on a known live and correctly wired receptacle. Do not use if the tester appears
attached to the circuit being tested could interfere with the tester, clear the circuit before testing.
damaged in any way. The tester is intended for indoor use only. Other equipment or devices
attached to the circuit being tested could interfere with the tester, clear the circuit before testing.
damaged in any way. The tester is intended for indoor use only. Other equipment or devices
This tester only detects common wiring problems. Always consult a qualified electrician to resolve
attached to the circuit being tested could interfere with the tester, clear the circuit before testing.
This tester only detects common wiring problems. Always consult a qualified electrician to resolve
attached to the circuit being tested could interfere with the tester, clear the circuit before testing.
wiring problems.
This tester only detects common wiring problems. Always consult a qualified electrician to resolve
wiring problems.
This tester only detects common wiring problems. Always consult a qualified electrician to resolve
WIRING CONFIGURATION TESTING
Conditions indicated: wiring correct, open ground, reverse polarity, open hot, open neutral and hot/
ground reversed.
Conditions NOT indicated: quality of ground, multiple hot wires, combinations of defects, reversal of
grounded and grounding conductors.
All appliances or equipment on the circuit being tested should be unplugged to help reduce the
possibility of erroneous readings.
STANDARD RECEPTACLES
1. Verify tester operation by testing on a known live and correctly wired receptacle.
2. Plug tester into receptacle.
3. Compare the illuminated lights on the tester to the key code printed on the tester.
4. If the tester indicates that the receptacle is not wired correctly, consult a qualified electrician.
GFCI RECEPTACLES
1. Check the GFCI receptacle user manual for information on how the specific receptacle operates prior to
using this tester.
2. Insert the tester into the receptacle under test to check for correct wiring (See FIG. 1). Lights on the
tester should illuminate.
3. Press the "TEST" button on the GFCI receptacle.
Did the GFCI trip and the lights on the tester go dark?
YES:
Reset the GFCI by pressing the reset button. Proceed to step 4.
NO:
The GFCI is not operating properly or the receptacle is miswired. Consult a qualified electrician.
4. Press and hold the test button on the tester for 7 seconds.
Did the GFCI trip and the lights on the tester go dark?
YES:
Reset the GFCI by pressing the reset button. The GFCI appears to be operating properly.
NO:
The GFCI is not operating properly or the receptacle is miswired. Consult a qualified electrician.
DISPOSAL / RECYCLE
Do not place equipment and its accessories in the trash. Items must be properly disposed of in accordance with local regulations. Please see www.epa.gov/recycle
for additional information.
Weight: 1.2 oz (33 g)
Pollution degree: 2
Safety Rating: CAT II 300V
Drop Protection: 6.6 ft. (2 m)
CLEANING
Wipe with a clean, dry lint-free cloth.
Do not use abrasive cleaners or solvents.