STE-6000 Series Room Temperature Sensors 3 Applications Guide
Wiring
Connect wires as shown for the relevant model.
STE-6013
STE-6012
Common (Ground)
Thermistor (10k Ohms)
D
B
C
10 VDC LED Supply (from Controller)
Common (Ground)
0–5 VDC Temperature Signal and (Momentary)
SENSOR-ON (0 VDC) or SENSOR-OFF (> 5 VDC)
D
B
C
A
0–5 VDC Setpoint Signal
7.5 VDC (Setback/Setup) or
12 VDC (Normal/Override) Supply (from Controller)
STE-6011
Thermistor (10k Ohms)
(Wires are
interchangeable)
(Override
Button)
{
{
{
{
NOTE: In the STE-6012/6016, pressing the Down buon
momentarily sends 0 VDC to the controller for
a SENSOR-ON signal; pressing the Up buon
sends greater than 5 VDC for a SENSOR-OFF
signal. When in normal/override mode, pressing
the Down or Up buon raises or lowers the
setpoint voltage. When in setback/setup mode,
pressing either buon selects override mode.)
STE-6019/6020
Common (Ground)
Thermistor (10k Ohms)
A
B
C
Potentiometer
(Override
Button)
D
10 VDC LED Supply (from Controller;
for STE-6020 Only)
More Information
For additional specications, see the STE-6000 Data
Sheet.
For mounting information, see the STE-6000 Installa-
tion Guide.
For an additional sample application of program-
ming override timers, adapt the information in the
Application Note AN0504F Programming Override
Timers section of the the Digital Designer’s Guide
(SP-022).
For applications requiring humidity sensing, the
THE-1002/1102/1105 humidity transmiers also
include the same type of thermistor as in the STE-
6000 series.
Maintenance
Careful installation will also ensure long-term reli-
ability and performance. Remove dust as necessary
from holes in top and boom. Clean with a so,
damp cloth and mild soap.
(For the STE-6010/6014/6015/6016/6017/6018, see the
next page. )