STE-6000 Series Room Temperature Sensors 9 Applications Guide
Setpoint Voltage Input (STE-6014/17/18/19/20 only)
1. In the BACstage soware main menu, select
Objects > Inputs.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Select Object Type: Analog if it is not the default.
5. Select Device > Device Tables > Table x (4 or 5).
6. Select Units: °F or °C.
7. Click End Edit.
8. Click Yes for “Send Update Notication Now?”
9. In the BACstage soware main menu, select
Device > Device Tables > Table x.
10. Click Edit.
11. Enter the following values in Table x:
NOTE: In the Adobe Acrobat le of this
document, you can use the table on page
10 to copy and paste the 128 lines into the
appropriate section of the BACstage *.BAC
panel le (instead of typing in the values
from the table below).
Index Value
1 54.0
2 54.3
3 54.6
4 54.9
5 55.2
6 55.5
7 55.8
8 56.1
9 56.4
10 56.7
11 57.1
12 57.4
13 57.7
14 58.1
15 58.4
BACstage
Thermistor Input (All)
NOTE: On the controller board, turn o the 10,000
ohm pull-up resistor (for STE-6012/6016
only).
1. In the BACstage soware main menu, select
Objects > Inputs.
2. Click Edit.
3. Type in a name in the Description eld (up to 32
characters) and/or Label eld (up to 16 characters).
NOTE: No two labels or descriptions in a controller
can be identical.
4. Select Object Type: Analog if it is not the default.
5. Select Device Type: KMC10K Type II.
6. Select Units: °F or °C.
7. Click End Edit.
8. Click Yes for “Send Update Notication Now?”
9. In the BACstage soware main menu, select
Device > Device Tables > KMC10K Type II Table.
10. Click Edit.
11. Click Defaults (values will ll in).
12. Click End Edit.
13. Click Yes for “Send Update Notication Now?”
14. Click OK.
Setpoint Voltage Input (STE-6012/6016 only)
NOTE: On the controller board, turn o the 10,000
ohm pull-up resistor.
1. In the BACstage soware main menu, select
Objects > Inputs (if the screen was closed
previously).
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Select Object Type: Analog if it is not the default.
5. Select Device Type: Volts 0–5.
6. Click End Edit.
7. Click Yes for “Send Update Notication Now?”
8. Click OK.