STE-6000 Series Room Temperature Sensors 8 Applications Guide
NOTE: For an additional sample application
of programming override timers, adapt
the information in the Application Note
AN0504F Programming Override Timers
section of the the Digital Designer’s Guide
(SP-022).
Supply Output (STE-6012/6016 only)
NOTE: The STE-6012/6016 is powered from the
controller output. A supply of 7.5 volts DC
puts the sensor in setback/setup mode and
12 volts puts it in normal/override mode.
1. In the WinControl soware main menu, select
Control > Output.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Select Units.
5. Select Type: Analog if it is not the default.
6. Select 0–10 Volts.
NOTE: This only sets the scale; the actual voltage
may go up to 12 volts DC.
7. Leave the rest of defaults.
8. Click OK.
9. Click End Edit.
10. Click OK.
Optional Control Basic (STE-6012/6016 only)
1. In the WinControl soware main menu, select
Control > Control Basic.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Place an x in the On column.
5. Click End Edit.
6. Click once in the # column.
7. Type in program lines (see the following
example).
NOTE: This is only an example. Details need to t
the controller conguration.
10 REM *** SETPOINT RANGE FOR ROOM SENSOR
***
20 REM *** RANGE IS 40 - 90 DEGREES FAHR-
ENHEIT ***
30 VAR2 = IN2 / 0.1 + 40
40 REM *** VAR2 IS THE ROOM SETPOINT
(FROM LINE 1 IN VARIABLE SCREEN) ***
50 REM *** IN2 IS SETPOINT VOLTAGE FROM
SENSOR (FROM LINE 2 IN INPUT SCREEN)
***
NOTE: The STE-6012/6016 is powered by the
controller on terminal D or the green wire.
With 7.5 VDC applied, the sensor is in
setback/setup mode; with 12 VDC applied,
the sensor is in normal/override mode.
Pressing the Down buon momentarily
sends 0 VDC to the controller for a
SENSOR-ON signal; pressing the Up buon
sends greater than 5 VDC for a SENSOR-
OFF signal. When in normal/override
mode, pressing the Down or Up buon
raises or lowers the setpoint voltage. When
in setback/setup mode, pressing either
buon selects override mode.
60 REM *** IN1 IS ROOM TEMP VOLTAGE FROM
SENSOR (FROM LINE 1 IN INPUT SCREEN)
***
70 REM *** VAR4 IS THE OVERRIDE (FROM
LINE 2 IN VARIABLE SCREEN) ***
80 REM *** USE BUTTON ON SENSOR TO START
OVERRIDE (VAR4) ***
90 IF SENSOR-ON( IN1 ) OR SENSOR-OFF( IN1
) THEN START VAR4
100 IF TIME-ON( VAR4 ) > 2:00:00 THEN
STOP VAR4
110 END
NOTE: For Celsius, use these lines for 10 through
30 instead.
10 REM *** SETPOINT RANGE FOR ROOM SENSOR
***
20 REM *** RANGE IS 4 - 32 DEGREES CEL-
SIUS ***
30 VAR2 = IN2 / 0.17857 + 4
8. Click Send.
9. Click OK.
10. Click Close.
11. Click OK.