STE-6000 Series Room Temperature Sensors 7 Applications Guide
Setpoint Voltage Input (STE-6014/17/18/19/20 only)
1. In the WinControl soware main menu, select
Control > Inputs.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Click Units (which opens the Congure Inputs
screen).
5. Select Type: Analog if it is not the default.
6. Select Table.
7. Click OK.
8. Click End Edit.
9. Click OK.
10. In the WinControl soware main menu, select
Control > Tables.
11. Click Unused in the rst available column.
12. Select Deg. F.
13. Click OK.
14. Enter the following values under Table x and Deg.
F:
Table x
[1 or next available number]
Deg. F
1 0.00 54
2 0.32 58
3 0.77 62
4 1.14 66
5 1.47 70
6 1.74 74
7 1.97 78
8 2.16 82
9 2.31 86
10 2.42 90
11 5.00 90
15. Click OK.
Setpoint Variable (STE-6012/14/16/17/18/19/20 only)
1. In the WinControl soware main menu, select
Control > Setpoint/Variables.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Click Units (which opens the Congure Variables
screen).
5. Select Type: Analog if it is not the default.
6. Select Degrees Fahrenheit (or Celsius).
7. Set Format to 0.
8. Click OK.
9. Click End Edit.
10. Click OK.
Override Input (STE-6012/13/15/16/17/18/19/20 only)
1. In the WinControl soware main menu, select
Control > Setpoint/Variables.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Click Units (which opens the Congure Variables
screen).
5. Select Type: Digital.
6. Select O/On (or No/Yes, Stop/Start, Dis/Enabled
according to preference).
7. Click OK.
8. Click End Edit.
9. Click OK.