EasyManuals Logo

KNX GIRA User Manual

KNX GIRA
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Dimming actuator
Electronic transformers with LV-LED 20 ... 100 W
Inductive capacitive mixed load is not permitted.
With setting "LED trailing edge phase control" the connection power for HV-LED lamps
and electronic transformers with LV-LED doubles.
Power consumption 110 V per output
Incandescent lamps 20 ... 250 W
HV halogen lamps 20 ... 250 W
HV-LED lamps typ. 3 ... 50 W
Compact fl lamp. typ. 3 ... 50 W
Inductive transformers 20 ... 250 VA
Inductive transformers with LV-LED 20 ... 50 VA
Electronic transformers 20 ... 250 W
Electronic transformers with LV-LED 20 ... 50 W
Inductive capacitive mixed load is not permitted.
With setting "LED trailing edge phase control" the connection power for HV-LED lamps
and electronic transformers with LV-LED doubles.
Power boosters See power booster instructions
Connection
single stranded 0.5 ... 4 mm²
Finely stranded without conductor sleeve 0.5 ... 4 mm²
Finely stranded with conductor sleeve 0.5 ... 2.5 mm²
Fitting width 72 mm / 4 module
KNX
KNX medium TP256
Commissioning mode S-mode
Rated voltage KNX DC 21 ... 32 V SELV
Current consumption KNX 15 mA
Connection mode KNX device connection terminal
Dimming actuator, 2-gang, order no. 2172 00
Rated voltage AC 110 ... 230 V ~
Mains frequency 50 / 60 Hz
Power loss max. 4 W
Standby power max. 0.8 W
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Power consumption 230 V per output
Incandescent lamps 20 ... 300 W
HV halogen lamps 20 ... 300 W
HV-LED lamps typ. 3 ... 60 W
Compact fl lamp. typ. 3 ... 60 W
Inductive transformers 20 ... 300 VA
Inductive transformers with LV-LED 20 ... 100 VA
Electronic transformers 20 ... 300 W
11 / 16
32575362 10867485 04.12.2019

Other manuals for KNX GIRA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KNX GIRA and is the answer not in the manual?

KNX GIRA Specifications

General IconGeneral
Protection ClassIP20
Ambient Temperature-5 °C to +45 °C
Communication ProtocolKNX
MountingDIN Rail
Number of ChannelsDepends on model