Setting voltage point back
to utility source when
selecting “SBU” (SBU
priority) or “SUB” (solar
first) in program 01.
default setting: 46V
Setting range is from 44V to 57V
and increment of each click is 1V.
5% (default)
If “WECO battery” is selected in
program 05, the setting value will
be fixed at 5% of connected
battery capacity.
13
Setting voltage point back
to battery mode when
selecting “SBU” (SBU
priority) or “SUB” (solar
first) in program 01.
Battery fully charged
The setting range is from 48V to
64V and increment of each click is
1V.
default setting: 54V
10% (default)
If “WECO battery” is selected in
program 5, this parameter value
will be displayed in percentage and
value setting is based on battery
capacity percentage. The setting
range is from 10% to 100%.
Increment of each click is 5%.
16
Charger source priority:
To configure charger
source priority
If this inverter/charger is working in Line, Standby or Fault mode,
charger source can be programmed as below:
Solar first
Solar energy will charge battery as
first priority.
Utility will charge battery only
when solar energy is not available.
Utility first
Utility will charge battery as first
priority. Solar energy will charge
battery only when utility power is
not available.