aaguilarSep 13, 2025
What to do if my Kohler 16EKOZD Portable Generator breaker is not charged?
- MMichelle LopezSep 13, 2025
Verify that the motor operator is receiving voltage at the appropriate contacts, allowing it to wind the spring.
What to do if my Kohler 16EKOZD Portable Generator breaker is not charged?
Verify that the motor operator is receiving voltage at the appropriate contacts, allowing it to wind the spring.
How to address fuel filter restriction in my Kohler Portable Generator?
If the fuel filter of your Kohler Portable Generator is restricted, clean or replace the fuel filter. The cause is fuel filter restriction.
What to do if my Kohler 16EKOZD runs out of fuel or the fuel valve is off?
If your Kohler Portable Generator's fuel tank is empty or the fuel valve is shut off, add fuel and move the fuel valve to the ON position. This is because the fuel tank is either empty, or the fuel valve is shut off.
How to resolve PGEN communication not operational in Kohler 16EKOZD Portable Generator?
In Controller Config --> Communication Setup, verify the PGEN Nodes Online is at least 2. If so, continue troubleshooting at Step 8 otherwise, continue on to Step 2.
What to do if my Kohler Portable Generator bus sensing is not connected?
Verify that the bus sensing wiring is connected to the load side of the motor-operated breaker for this generator.
How to resolve breaker status feedback is not valid, no bus sensing in Kohler Portable Generator?
Verify the wiring on the circuit breaker to ensure it is connected correctly. Verify bus wiring for all nodes. Verify the generator output is connected to the line side of the generator breaker.
What to do if the low oil pressure switch is inoperative on my Kohler Portable Generator?
If the low oil pressure switch is inoperative on your Kohler Portable Generator, replace the low oil pressure switch and check the engine for damage. This is because the low oil pressure switch is inoperative.
What to do if the fuel injection timing is out of adjustment on my Kohler 16EKOZD?
If the fuel injection timing is out of adjustment on your Kohler Portable Generator, adjust the fuel injection timing. This is due to fuel injection timing being out of adjustment.
How to resolve baud rate misconfigured in Kohler 16EKOZD?
In Controller Config --> Communication Setup, verify that the baud rate of all generators on the network matches. The default is 57,600 baud.
How to fix a faulty ground connection on my Kohler 16EKOZD Portable Generator?
If you find a faulty ground connection in your Kohler Portable Generator, clean and retighten the connection. The cause is a faulty ground connection.
Model | 16EKOZD |
---|---|
Type | Portable Generator |
Fuel Type | Gasoline |
Voltage | 120/240V |
Frequency | 60 Hz |
Warranty | 3 Years Limited |
Specifies the type of generator sets covered in this manual.
Lists essential checks before starting the generator set.
Describes the features of the Decision-Maker® 3500 controller.
Explains how the controller functions and responds to inputs.
Explains how to monitor and program the controller via PC.
Covers general safety practices and basic maintenance.
Provides a maintenance schedule for specific generator models.
Provides a maintenance schedule for specific generator models.
Details the procedure for inspecting and replacing the seawater pump impeller.