TP-6953 7/19 83Section 2 Operation
SiteTecht Parameter
Write
Access
Units
Decision-Maker
r
3500
User Interface
Notes
Analog Resistive I nput Metered Value None Measurement: ###.# Ohms The current value of the
input (scaled to the units
of the function ID)
Analog Resistive Input Metered Relative Value None The value of the input
relative to the full range
of the input
Analog Resistive Input Enabled Always Input Enabled: On/Off Indicates whether this
input is enabled
Analog Resistive I nput Switch Logic Always Thetypeofswitchthatis
connected to the input,
where “normal” refers to
the non-activated state.
Analog Resistive Input Function Always Indicates the functionality
of this IO point
Analog Resistive Input Protectives Enabled Always Low Warning: On/Off
High Warning: On/Off
Low Shutdown: On/Off
High Shutdown: On/Off
Indicates which of the
protectives are active for
this input
Analog Resistive Input Event Always The parameter ID
defining the function for
this input
Analog Resistive Input Sensor Always Sensor Type: The type of sensor
connected to the input
Analog Resistive Input Low Protective Inhibit Delay Always s Low Protect Inhibit: ##s The time, after crank
disconnect, before the
protectives for this input
are monitored; if 0,
protectives are monitored
even when the engine is
stopped
Analog Resistive Input High Protective Inhibit Delay Always s High Protect Inhibit: ##s The time, after crank
disconnect, before the
protectives for this input
are monitored; if 0,
protectives are monitored
even when the engine is
stopped
Analog Resistive Input Delay Always s Thetimethattheinput
must be active before a
status change is
indicated
Analog Resistive Input Inhibit Delay Always s Thetimethattheinput
must be active before a
status change is
indicated
Analog Resistive Input Normal Delay Always s Thetimethattheinput
must be within its normal
operating range before all
protectives are
considered good
Analog Resistive Input Low Warning Delay Always s Low Warning Delay: ##s Thetimethattheinput
must be within its
warning operating range
before a warning
protective is indicated
Analog Resistive Input Critically Low Warning Delay Always s Thetimethattheinput
must be within its
warning operating range
before a warning
protective is indicated
Analog Resistive Input High Warning Delay Always s High Warning Delay: ##s Thetimethattheinput
must be within its
warning operating range
before a warning
protective is indicated
Analog Resistive Input Critically High Warning Delay Always s Thetimethattheinput
must be within its
warning operating range
before a warning
protective is indicated