TP-6805 8/15 49Section 4 Controller
SiteTech Group Notes [
Default
Setting
Adjustment
Range *
UnitsParameter
Network Configuration
DHCP Enabled True or False True
OnCue
Plus
Static IP Address 0.0.0.0 --
255.255.255.255
0.0.0.0
Static Subnet Mask 0.0.0.0 --
255.255.255.255
0.0.0.0
Static Default Gateway 0.0.0.0 --
255.255.255.255
0.0.0.0
Static DNS Server 1 0.0.0.0 --
255.255.255.255
0.0.0.0
Static DNS Server 2 0.0.0.0 --
255.255.255.255
0.0.0.0
Server Host Name devices.kohler.com devices.
kohler.
com
Network Status
IP Address Read Only 0.0.0.0
OnCue
Plus
Subnet Mask Read Only 0.0.0.0
Default Gateway Read Only 0.0.0.0
DNS Server 1 Read Only 0.0.0.0
DNS Server 2 Read Only 0.0.0.0
MAC Address Read Only N/A
Connected Server IP Address Read Only 0.0.0.0
Network Connection Established Read Only False
Media Connected Read Only False
Rbus Network
Rbus Active Read Only False
Rbus Connection Count Read Only 0
Rbus Net Cycle Time ms Read Only 100
Rbus Timeouts Read Only 0
Rbus Errors Read Only 0
Rbus Devices B1
Rbus Devices B1 Serial Number Read Only N/A
RXT,
PIM, or
Load
Mgmt
w
Rbus Devices B1 Type Read Only N/A
Rbus Devices B1 Communication
Errors
Read Only N/A
Rbus Devices B1 Communication
Timeouts
Read Only N/A
Rbus Devices B1 Modbus Id Read Only N/A
Rbus Devices B1 Last
Connection Date
Read Only N/A
Rbus Devices B1 Firmware
Version
Read Only N/A
Rbus Devices B1 Connected Read Only N/A
* Read Only = Not adjustable
[ Notes indicate applicability to genset model and accessories. N/A = Not applicable to these generator s ets.
] See TT-1584 for more information about digital inputs and outputs.
w Load management device (LCM, load shed kit, or RXT with combined interface/ load management board)