EasyManuals Logo

Kohler 4EFOZ Operation Guide

Kohler 4EFOZ
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
TP-6068 10/02
28 Section 4 Troubleshooting
Section or
Publication
Reference*
Recommended ActionsProbable Causes
Trouble Symptoms
Section or
Publication
Reference*
Recommended ActionsProbable Causes
Excessive or
abnormal noise
High fuel
consumption
Low oil
pressure
Overheats
Lacks power
Stops
suddenly
No or low
output v oltage
Starts hard
Cranks but
does not start
Does not
crank
Fuel System
x x Fuel tank empty or fuel valve shut off Add fuel and move the fuel valve to the ON position.
x x x x Fuel filter restriction Clean or replace the fuel filter. Eng. O/M
x Fuel solenoid inoperative
Troubleshoot the fuel solenoid.[
Eng. S/M
x x x Air in fuel system (diesel only) Bleed the diesel fuel system. Eng. O/M
x x x
Fuel or fuel injectors dirty or faulty
(diesel only)
Clean, test, and/or replace the inoperative fuel injector.[
Eng. S/M
x x x x
Fuel injection timing out of adjustment
(diesel only)
Adjust the fuel injection timing.[
Eng. S/M
x x x
Fuel feed or injection pump inoperative
(diesel only)
Rebuild or replace the injection pump.[
Eng. S/M
Generator
x
AC output circuit breaker open Reset the breaker and check for AC voltage at the generator
side of the circuit breaker.
x
Transfer switch test switch in the OFF
position
Move the transfer switch test switch to the AUTO position. ATS O/M
x
Wiring, terminals, or pin in the exciter
field open
Check for continuity. Gen. S/M, W/D
x
Main field (rotor) inoperative (open or
grounded)
Test and/or replace the rotor.[
Gen. S/M
x Stator inoperative (open or grounded)
Test and/or replace the stator.[
Gen. S/M
x Vibration excessive
Tighten loose components.[
x x Voltage regulator out of adjustment Adjust the voltage regulator. Gen. S/M
x x
Voltage regulator inoperative Replace the voltage regulator fuse, If the fuse blows again,
troubleshoot the voltage regulator.
Gen. S/M
Lube System
x x x Oil level low Restore the oil level. Inspect the generator set for oil leaks. Eng. O/M
x Low oil pressure shutdown Check the oil level. Eng. O/M
x x x x
Crankcase oil type incorrect for
ambient temperature
Change the oil. Use oil with a viscosity suitable for the operating
climate.
Eng. O/M
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram
[ Have an authorized service distributor/dealer perform this service.

Other manuals for Kohler 4EFOZ

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 4EFOZ and is the answer not in the manual?

Kohler 4EFOZ Specifications

General IconGeneral
BrandKohler
Model4EFOZ
CategoryPortable Generator
LanguageEnglish

Related product manuals