EasyManua.ls Logo

Kohler 6VSG

Kohler 6VSG
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 TP-6842 9/21
1.6.2 Fuel Pipe Size
Ensure that the fuel pipe size and length meet the specifications in Figure 5. Measure the pipe length from the primary gas
pressure regulator to the pipe connection on the generator set fuel inlet. Add 2.4 m (8 ft.) to the measured length for each
90 degree elbow. Compare the total pipe length with the chart in Figure 5 to find the required pipe size.
Contact local LPG or natural gas provider for LPG or natural gas installation information.
Minimum Gas Pipe Size Recommendation, in. NPT
Pipe Length,
m (ft.)
Natural Gas
(115,000 Btu/hr.)
LPG
(106,000 Btu/hr.)
8 (25)
¾
½
15 (50)
1
¾
30 (100)
1
¾
46 (150)
1
¾
61 (200)
1
1
Figure 5 Fuel Pipe Size Recommandations
Model
Fuel Type
% Load
Fuel Consumption,
m
3
/hr. (cfh)
6VSG
Natural Gas
100
3.3 (116)
75
2.7 (96)
50
2.1 (75)
25
1.8 (62)
LPG
100
1.2 (42)
75
1.0 (35)
50
0.9 (32)
25
0.7 (27)
Nominal fuel rating:
Natural gas:
37 MJ/m
3
(1000 Btu/ft.
3
)
LPG
93 MJ/m
3
(2500 Btu/ft.
3
)
LPG conversion factors:
8.58 ft.
3
= 1 lb.
0.535 m
3
= 1 kg
36.39 ft.
3
= 1 gal.
Figure 6 Fuel Consumption

Other manuals for Kohler 6VSG

Related product manuals