Utility power for battery charging is connected to the generator set. Before servicing the battery, disconnect the utility power by
opening the circuit breaker, which is typically located in the customer's electrical distribution box.
Clean the battery and cables and tighten battery terminals using the service schedule recommendations. To prevent corrosion,
maintain tight, dry electrical connections at the battery terminals. To remove corrosion from battery terminals, disconnect the
cables from the battery and scrub the terminals with a wire brush. Clean the battery and cables with a solution of baking soda
and water. After cleaning, flush the battery and cables with clean water and wipe them with a dry, lint-free cloth.
After reconnecting the battery cables, coat the battery terminals with petroleum jelly, silicone grease, or other nonconductive
grease.