117
Section 7 Decision-Makerr 6000 ControllerTP-6356 4/12
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Cyclic Cranking 8 1--6 crank cycles
10--30 sec. crank on
1--60 sec. pause
3
15 sec.
15 sec.
Dead Bus Sensing
Fault
10, 16 DEAD BUS
SENSE FAULT
Not adjustable
Defined Common
Fault
(each input value is
set separately)
10 DEFINED
COMMON
FAULT
RDO-3
(lead 32A)
Default shutdowns
include:
Emergency stop
High coolant temp
Low oil pressure
Overcrank
Overspeed
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Defined Common
Warning
(each input value is
set separately)
10 DEFINED
COMMON
WARN
RDO-24 30 sec.
inhibit,
5 sec. delay
0--60 0--60
Derate Active 10 ENGINE
DERATE
ACTIVE
RDO-20 Not adjustable
Digital Aux. Input
D01--D21
9, 10 USER-DEFINED
D01--D21
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Digital Aux. Input
D01 (see Battery
Charger Fault) [
—
Digital Aux. Input
D02 (see Low Fuel
Warning) [
—
Digital Aux. Input
D03 (see Low
Coolant
Temperature) [
—
Digital Aux. Input
D04 (see Field
Overvoltage)
—
Digital Aux. Input
D05 (see Breaker
Closed)
—
Digital Aux. Input
D06 (see Enable
Synch)
—
Digital Aux. Input
D09 (see Low Fuel
Shutdown)
—
Digital Aux. Input D14
(see Low Coolant
Level) [
—
Digital Aux. Input
D15 (see Remote
Shutdown)
—
Digital Aux. Input
D21 (see Idle [speed]
Mode Function)
—
Duplicate PGEN ID 10, 16 DUPLICATE
PGEN
WARNING
Not adjustable
ECM Yellow Alarm * 10 ECM YELLOW
ALARM
Not adjustable
ECM Red Alarm * 10 ECM RED
ALARM
Not adjustable
EEPROM Write
Failure
10 EEPROM WRITE
FAILURE
Not adjustable
Emergency Stop
Shutdown
10 EMERGENCY
STOP
RDO-2
(lead 48)
Fixed 0 0 Not adjustable
* DD/MTU engine with MDEC/ADEC
[ NFPA applications
] 3x (times) energize time shown in Menu 17