117
Section 7 Decision-Makerr 6000 ControllerTP-6356 4/12
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Cyclic Cranking 8 1--6 crank cycles
10--30 sec. crank on
1--60 sec. pause
3
15 sec.
15 sec.
Dead Bus Sensing
Fault
10, 16 DEAD BUS
SENSE FAULT
Not adjustable
Defined Common
Fault
(each input value is
set separately)
10 DEFINED
COMMON
FAULT
RDO-3
(lead 32A)
Default shutdowns
include:
Emergency stop
High coolant temp
Low oil pressure
Overcrank
Overspeed
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Defined Common
Warning
(each input value is
set separately)
10 DEFINED
COMMON
WARN
RDO-24 30 sec.
inhibit,
5 sec. delay
0--60 0--60
Derate Active 10 ENGINE
DERATE
ACTIVE
RDO-20 Not adjustable
Digital Aux. Input
D01--D21
9, 10 USER-DEFINED
D01--D21
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Digital Aux. Input
D01 (see Battery
Charger Fault) [
Digital Aux. Input
D02 (see Low Fuel
Warning) [
Digital Aux. Input
D03 (see Low
Coolant
Temperature) [
Digital Aux. Input
D04 (see Field
Overvoltage)
Digital Aux. Input
D05 (see Breaker
Closed)
Digital Aux. Input
D06 (see Enable
Synch)
Digital Aux. Input
D09 (see Low Fuel
Shutdown)
Digital Aux. Input D14
(see Low Coolant
Level) [
Digital Aux. Input
D15 (see Remote
Shutdown)
Digital Aux. Input
D21 (see Idle [speed]
Mode Function)
Duplicate PGEN ID 10, 16 DUPLICATE
PGEN
WARNING
Not adjustable
ECM Yellow Alarm * 10 ECM YELLOW
ALARM
Not adjustable
ECM Red Alarm * 10 ECM RED
ALARM
Not adjustable
EEPROM Write
Failure
10 EEPROM WRITE
FAILURE
Not adjustable
Emergency Stop
Shutdown
10 EMERGENCY
STOP
RDO-2
(lead 48)
Fixed 0 0 Not adjustable
* DD/MTU engine with MDEC/ADEC
[ NFPA applications
] 3x (times) energize time shown in Menu 17

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 6000 and is the answer not in the manual?

Kohler Decision-Maker 6000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 6000
CategoryPortable Generator
LanguageEnglish

Related product manuals