Section 7 Decision-Makerr 6000 Controller TP-6356 4/12
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Enable Synch D06 9, 10,
16
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Engine Cooldown
(see Time Delay--)
—
Engine Stalled 10 ENGINE
STALLED
Not adjustable
Engine Start
(see Time Delay--)
—
EPS (Emergency
Power System)
Supplying Load
10 EPS
SUPPL YING
LOAD
RDO-18 Fixed 1% of rated
line current
Not adjustable
External Breaker Trip 10 EXTRNL
BREAKER
TRIP
RDO-31 Not adjustable
Extra PGEN Node 10, 16 EXTRA PGEN
NODE
Fixed Not adjustable
Field Overvoltage
D04
(M4, M5, M7, or M10
alternator only)
9, 10 FIELD
OVERVOLTAGE
D04
Fixed 1 sec.
inhibit,
15 sec.
delay
Not adjustable
First On Fault 9, 16 FIRST ON
FAULT
0.5 sec.
delay
0.5--
10
Generator Set
Parameter Warning
7 GENSET
PARAM
WARNING
Not adjustable
Generator Set
Running
10 RDO-22
(lead 70R)
Not adjustable
Generator Set Serial
Number Warning
20 GENSET S/N
WARNING
Not adjustable
Ground Fault
Detected (Digital
Input)
9, 10 GROUND
FAULT
RDO-17 Not adjustable
High Battery Voltage 10 HIGH
BATTERY
VOL TAGE
14.5--16.5 V (12 V)
29--33 V (24 V)
16 V (12 V)
32 V (24 V)
10
High Coolant
Temperature
Shutdown
10 HI COOL TEMP
SHUTDOWN
(lead 36) Fixed 30 5 Not adjustable
High Coolant
Temperature Warning
10 HI COOL TEMP
WARNING
RDO-6
(lead 40)
Fixed 30 0 Not adjustable
High Oil Temperature
Shutdown
9, 10 HI OIL TEMP
SHUTDOWN
Fixed 30 5 Not adjustable
High Oil Temperature
Warning *
9, 10 HI OIL TEMP
WARNING
Fixed 30 0 Not adjustable
Idle (speed) Mode
Function D21
9, 10 Fixed inhibit time
0--600 sec. delay or
9.99 (infinite)
0 sec.
inhibit,
60 sec.
delay
0 0--600
In Synch (Dwell
Time)
10 IN SYNCH RDO-27 0.3 sec. 0.1--
30
Intake Air
Temperature
Shutdown *
10 INTAKE AIR
TEMP SDWN
Fixed 30 0 Not adjustable
Intake Air
Temperature
Warning *
10 INTAKE AIR
TEMP WARN
Fixed 30 5 Not adjustable
Internal Fault
Shutdown
10 INTERNAL
FAULT
Not adjustable
J1939 CAN
Shutdown
10 J1939 CAN
SHUTDOWN
Not adjustable
Key Switch Locked 10 KEY SWITCH
LOCKED
RDO-21 Not adjustable
* DD/MTU engine with MDEC/ADEC
[ NFPA applications
] 3x (times) energize time shown in Menu 17

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 6000 and is the answer not in the manual?

Kohler Decision-Maker 6000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 6000
CategoryPortable Generator
LanguageEnglish

Related product manuals