3.11.1 Lubrication System
Prepare the engine lubricating system for storage as follows.
Note:
Kohler recommends the use of Kohler genuine oil and filters.
1. Run the generator set for a minimum of 30 minutes to bring it to normal operating temperature.
2. Stop the generator set.
3. With the engine still warm, drain the oil from the crankcase.
4. Remove and replace the oil filter.
5. Refill the crankcase with oil suited to the climate.
6. Run the generator set for two minutes to distribute the clean oil.
7. Stop the generator set.
8. Check the oil level and adjust, if needed.
3.11.2 Cooling System
Prepare the cooling system for storage as follows:
1. Check the coolant freeze protection using a coolant tester.
2. Add or replace coolant as necessary to ensure adequate freezing protection. Use the guidelines included in the engine
operation manual.
3. Run the generator set for 30 minutes to redistribute added coolant.
3.11.3 Diesel Fuel System Storage
1. Fill the fuel tank with #2 diesel fuel.
2. Condition the fuel system with compatible additives to control microbial growth.
3. Change the fuel filter/separator and bleed the fuel system. See the engine owner’s manual.
3.11.4 Gaseous Fuel System Storage
1. Start the generator set.
2. With the generator set running, shut off the gas supply.
3. Run the generator set until the engine stops.
4. Place the generator set master switch in the OFF/RESET position.

Table of Contents

Other manuals for Kohler KG150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler KG150 and is the answer not in the manual?

Kohler KG150 Specifications

General IconGeneral
BrandKohler
ModelKG150
CategoryPortable Generator
LanguageEnglish

Related product manuals