G.F.C.I. Receptacle test
1. Start the engine.
2. Press the test button, then check the position of
the reset button.
1 Test button
2 Reset button
G.F.C.I. Reset
Button Position
after Test
G.F.C.I. Receptacle
Operation
3 Pop Out
Correct
4 Stay In
Incorrect
3. If G.F.C.I. operation is correct, push in the reset
button.
If the G.F.C.I. operates incorrectly, consult a
Kohler portable dealer.
Do not operate the generator with a faulty G.F.C.I.
circuit. Electric shock could occur. Have the gen-
erator repaired by a qualified mechanic.